sure connection. Low pressure and differential pressure units, models 

520-535,  540-543,  544-548,  are  also  available  with  an  optional 

surface  mounting  bracket.  Should  the  control  be  installed where  con-

densation is expected, vertical mounting is recommended as a means of 

keeping water away from switch terminals.

Never use the enclosure for leverage to hand tighten the pressure con-

nection.  Always use a wrench to tighten the pressure connection to the 

pipe.To prevent damaging the pressure sensor, use a back-up wrench 

to hold the hex nut in place when surface mounting.  

On models supplied with an external manual reset button, be sure to 

leave sufficient finger space over the reset button for the operator to 

reset the control. See Mounting Diagram.

WIRIng

DiScONNecT ALL SuppLy circuiTS befOre WiriNg.

  

eLecTricAL  rATiNgS  STATeD  iN  LiTerATure  AND  ON 

NAMepLATeS  SHOuLD NeVer  be  exceeDeD.  OVerLOAD 

ON  A  SWiTcH  cAN  cAuSe  fAiLure  ON  THe  firST  cycLe.  

 

Wire uNiTS AccOrDiNg TO NATiONAL AND LOcAL eLecTricAL 

cODeS. MAxiMuM recOMMeNDeD Wire Size iS 14 AWg. 

remove the two screws retaining the cover and cover gasket. A 1/2” NpT 

conduit connection is provided on the left hand side of the enclosure. 

Two cast-in knockouts for the 1/2” conduit are located on the side and 

back  of  the  enclosure.    These  can  easily  be  knocked  out  by  placing 

the  blade  of  a  screwdriver  in  the  groove  and  tapping  sharply  with  a  

hammer.  The  three  switch  ter minals  are  clear ly  labeled 

“common”,  “nor mally  open”  and  “nor mally  closed”.  for 

optional  switches  supplied  with  leadwires,  the  following  color  

coding applies:

Manual

DPDT

Reset

(Option 1530)

(Option 1010)

SPDT

SWT1

SWT2

 common

Violet

Violet

yellow

Normally Open

blue

blue

Orange

Normally closed black

black

red

gEnERAL

befOre  iNSTALLiNg,  cHecK  THe  SeNSOr  MODeL  SeLecTeD 
fOr cOMpATibiLiTy TO THe prOceSS MeDiA iN cONTAcT WiTH 
THe SeNSOr AND WeTTeD pArTS.

The H100 and H100K differential pressure switches are activated when 

a bellows, diaphragm or piston sensor responds to a pressure change. 

This response, at a pre-determined set point, actuates a single snap-

acting  switch,  converting  the  pressure  signal  into  an  electrical  signal. 

control set point may be varied by turning the internal adjustment hex. 

(See Adjustment -pArT ii).

prOOf preSSure* LiMiTS STATeD iN THe LiTerATure AND ON 

NAMepLATeS  MuST  NeVer  be  exceeDeD,  eVeN  by  SurgeS 

iN  THe  SySTeM.    OccASiONAL  OperATiON  Of  uNiT  up  TO 

prOOf  preSSure iS AccepTAbLe (e.g., STArT-up, TeSTiNg).  

cONTiNuOuS OperATiON SHOuLD NOT exceeD THe DeSigNATeD OVer 

rANge preSSure.

*Proof Pressure
The maximum pressure to which a pressure sensor may be occasionally 

subjected, which causes no permanent damage (e.g., start-up, testing).  

The unit may require re-gapping.

 

Tools needed

Adjustable Wrench

Screwdriver

Hammer (for alternate wire knockouts)

MounTIng

iNSTALL uNiT WHere SHOcK, VibrATiON AND TeMperATure 

fLucTuATiONS  Are  MiNiMAL.    OrieNT  uNiT  SO  THAT  MOiS-

Ture  iS  preVeNTeD  frOM  eNTeriNg  THe  eNcLOSure.    if 

uNiT iS  beiNg iNSTALLeD WHere HeAVy cONDeNSATiON iS expecTeD, 

VerTicAL MOuNTiNg (preSSure cONNecTiON DOWN) iS requireD. DO 

NOT MOuNT iN AMbieNT TeMperATureS exceeDiNg pubLiSHeD LiMiTS.

c o n t r o l s   m a y   b e   m o u n t e d   a n d   o p e r a t e d   i n   a n y  

position.  They may be surface mounted via the two mounting ears on 

either side of the enclosure, or directly to a rigid pipe by using the pres-

100 Series

Type  H100 

(Pressure Switch) 

 

Type H100K

(Differential Pressure)

IMP100-07

Please read all instructional literature carefully and thoroughly before starting.  Refer to the final page for the listing of Recommended 
Practices, Liabilities and Warranties.

Part I - Installation

U N I T E D   E L E C T R I C 
C O N T R O L S

Installation and Maintenance 

Instructions

Содержание 100 Series

Страница 1: ...E INSTALLING CHECK THE SENSOR MODEL SELECTED FOR COMPATIBILITY TO THE PROCESS MEDIA IN CONTACT WITH THE SENSOR AND WETTED PARTS The H100 and H100K differential pressure switches are activated when a bellows diaphragm or piston sensor responds to a pressure change This response at a pre determined set point actuates a single snap acting switch converting the pressure signal into an electrical signa...

Страница 2: ...eased by tightening adjustment lock onto it See diagram 1 Controls include uncalibrated reference scales for high low or mid range settings Adjustable Differential Models Model 15623 15731 15737 and control types with option code 1519 incorporate a snap switch with internal adjustment wheel Turning this wheel raises or lowers the pressure rise set point The fall set point remains constant Consult ...

Страница 3: ...2 188 189 6 62 168 1 1 2 190 194 6 63 168 4 1 2 218 274 6 56 166 6 1 4 358 376 7 03 178 6 1 4 483 486 7 56 192 0 1 2 488 489 6 62 168 1 1 2 490 494 6 63 168 4 1 2 520 525 8 44 214 4 1 2 530 535 8 00 203 2 1 2 540 548 8 34 211 8 1 8 560 564 6 62 168 1 2 Sanitary fitting 565 567 6 62 168 1 1 1 2 Sanitary fitting 610 616 7 00 177 8 1 4 680 6 97 177 0 1 4 701 706 6 57 166 9 1 4 15623 6 57 166 9 1 4 15...

Страница 4: ...testing is necessary for critical applica tions where damage could endanger property or personnel Electrical ratings stated in literature and on nameplate must not be exceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambient temp exceeding published...

Отзывы: