Installation, Operation and Maintenance Manual
Marvel Plus
18
Subject to change without notice.
120.5-IM (1018)
BMS Setup Screen
U01
Communications
Protocol : BACnet
Unit Ident : 001
Baud Rate : 19200
The Communications screen is used to set the type of
communications protocol to be used�
BMS Reset Function Screen
U01
BMS Reset
Function Enable
Supply Temp Setpt > NO
Duct Press Setpt
> NO
If either function on the BMS Reset Function Enable screen
is set to yes, it will allow BMS communications to perform
that function� The Reset would then be performed based on
the reset communications points in the communication point
list�
Change Password Screen
U01
Change Passwords
Level
1 >
0000
Technicians Menu
Fan Delays Screen
U01
Fan Delays
Startup
> 005s
Airflow Proof >
030s
Unit OFF Delay >
10s
The Fan Delays screen allows customer to set the amount of
delay in seconds for system startup, proof of air flow based
on the amount of time it takes the VFD to ramp up, and the
amount of time in seconds for the unit to turn off (allows for
dissipation of heat energy before shut down)�
Temperature Unit Screen
U01
Temperature Units
Mode > FAHRENHEIT
The Temperature Units screen allows customers to select
the temperature unit to be either Fahrenheit or Centigrade�