APPENDIX E. COMMUNICATIONS
HF25D LINEAR DC RESISTANCE WELDING CONTROL
990-333
E-9
Command
MONITOR {READ | SET}
<crlf>
[
parameter_name value
<crlf>]
<lf>
Control State
Any except while welding
Description
Provides control over the basic weld monitor settings of the Control schedule. When used
with the "READ" keyword, the basic weld monitor settings of the currently loaded schedule
are returned (see MONITOR under Control ORIGINATED COMMANDS). When the "SET"
keyword is used, the host may set (change) the value of one or more of the parameters of the
basic weld monitor settings pertaining to the currently loaded schedule. The following is a list
of valid literal substitutions for the parameter_name and value variables:
MONTYPE1
{ KA | V | KW }
Monitor Type for pulse 1
UPPER1 {
limit_value
}
Upper Limit for pulse 1
LOWER1 {
limit_value
}
Lower Limit for pulse 1
ACTION1
{ none | STOP | INHIBIT | APC }
Out of Limit Action for
pulse 1
MONTYPE2
{ KA | V | KW }
Monitor Type for pulse 2
UPPER2 {
limit_value
}
Upper Limit for pulse 2
LOWER2 {
limit_value
}
Lower Limit for pulse 2
ACTION2
{ none | STOP }
Out of Limit Action for pulse 2
P1LDLY1
{delay_value}
Pulse 1 Lower Delay Start Time Fo
Lower
Limit
P1LDLY2
{delay_value}
Pulse 1 Lower Delay End Time For
Lower
Limit
P1UDLY1
{delay_value}
Pulse 1 Upper Delay Start Time For
Upper
Limit
P1UDLY2
{delay_value}
Pulse 1 Upper Delay End Time For
Upper
Limit
P2LDLY1
{delay_value}
Pulse 2 Lower Delay Start Time For
Lower Limit
P2LDLY2
{delay_value}
Pulse 2 Lower Delay End Time For
Lower
Limit
P2UDLY1
{delay_value}
Pulse 2 Upper Delay Start Time For
Upper
Limit
P2UDLY2
{delay_value}
Pulse 2 Upper Delay End Time For
Upper
Limit
limit_value
is the parameter that specifies the range of the valid readings. If the reading was
within the range of the
limit_value
, no alarm will occur. If the reading was out of the valid
range, an alarm will occur. If the monitor type is KA, the
limit_value
is in unit of 1A. If the
monitor type is V, the
limit_
value is in unit of 1mV. If the monitor type is kW, the
limit_
value
is in unit of 1W. The valid number for
limit_value
is 1 through 9999 and 0 is for none.
The
delay_value
is the parameter that defines the time for the given period in 0.1ms. Valid
range is from 0 to 99. Lower delay value is only valid during WELD time. Upper delay value
is valid during UP time, WELD time, and DOWN time.
Содержание HF25A
Страница 9: ...HF25D DC RESISTANCE WELDING SYSTEM 990 333 ix ...
Страница 10: ......
Страница 20: ......
Страница 84: ...CHAPTER 6 CALIBRATION HF25D DC RESISTANCE WELDING SYSTEM 990 333 6 4 Final Calibration Setup ...
Страница 113: ......
Страница 129: ......
Страница 153: ......
Страница 171: ......