background image

GENERAL

This information is intended for the instruction of this low NOx
kit only. The Installation Instruction supplied with the appliance
are to be used for all other aspects of the installation.

WARNING: Improper installation, adjustment service, or main-

tenance can cause injury or property damage,
therefore, only a qualified installer or qualified serv-
ice personnel should perform this conversion.

INSPECTION

The following list details the parts included in this kit. Inspect
the kit to insure that all listed parts are included.

INSTALLATION

WARNING: Make sure both the gas and electric power are

shut-off.

1. Turn off electrical and gas to the unit.

2. Remove burner assembly at vestibule panel. Carefully move

assembly aside and provide adequate support to assembly. It
should not be necessary to disconnect any wiring.

3. Install a screen into each heat exchanger tube. (Refer to

Figure 1 and 2 for position of screen).

4. reinstall burner assembly to vestibule panel.

5. Remove label 035-11635-000 from the shipping box. Check

the natural gas.

6. Under "Rating After Conversion", write in the following;

a. Orifice size, as stamped on the orifice.

b. Maximum inlet pressure - 10.5" WC.

c. Minimum inlet pressure - 4.5" WC.

d. Manifold pressure - 3.5" WC.

e. Input, this will the input on the Rating Plate

INSTALLATION
INSTRUCTION

LOW NOx ACCESSORY

MODEL 1LN0802

Supersedes:  530.46-N1.1V (995)

530.46-N1.14V (496)

FOR SINGLE PACKAGE GAS / ELECTRIC AIR CONDITIONERS

1.5 THRU 5 TON

035-13942

WARNING: This accessory must not be used on units

that will be converted to  liquified propane

FIGURE 1 - POSITIONING OF SCREENS IN TUBES

FIGURE 2 - ASSEMBLY CROSS SECTION

SCREEN

POSITION

IN TUBE

CONTENTS OF KIT

ITEM QTY.

PART NO.

DESCRIPTION

1

1

035-11635-000

Convert and Modify Label

2

5

026-34598-000

NOx Screen

3

1

035-13942-000

Accessory Instruction Form

VESTIBULE

PANEL

MANIFOLD / BURNER

ASSEMBLY

HEAT EXCHANGER TUBE

(CROSS SECTION)

LOW NOx

SCREEN

INSERT

WARNING: For U.S. units, installation must be made in accordance with American Na-
tional Standard National Fuel Gas Code, ANSI Z223.1 - latest edition, unless superseded
by local codes. For Canadian installations, the conversion shall be carried out in accord-
ance with the requirements of the Provincial authorities having jurisdiction and in ac-
cordance with the CAN1-B149.1 and .2 installation codes.

WARNING: This conversion kit is to be installed by a qualified service agency in accord-
ance with the manufacturer’s instructions and all applicable codes and requirements of
the authority having jurisdiction. If the information in these instructions is not followed
exactly, a fire, explosion or production of carbon monoxide may result causing property
damage, personal injury or loss of life. The qualified agency performing this work as-
sumes responsibility for the proper conversion of this appliance with this kit.