76
12
Interface
76
In
te
rf
ac
e
Chapter
12
12-1.
RS-485 Interface
(RS-485 or SI/F
standard: not specified at the time of order)
RS-485 is an interface to read the indicated values and status of the F325 and to write the setting
values into the F325. This interface is convenient for processing such as controls, totals, and
records by connecting the F325 to a PLC, programmable display unit and so forth.
■
Communication specifications
Specifications
Message format:
Modbus-RTU, UNI-Format
Signal level:
Based on RS-485 Two-wire
Transmitting distance:
Approx. 1 km
Transmitting method:
Asynchronous, half duplex
Transmitting speed:
Selectable from 1200, 2400, 4800, 9600, 19200, 38400 bps
Number of connectible units: Maximum 32 (including one master unit)
Bit configuration:
Start bit
1bit
Character lengt Selectable from 7 or 8 bit
(8 bit for Modbus-RTU)
Stop bit
Selectable from 1 or 2 bit
Parity bit
Selectable from none, odd or even
Terminator
Selectable from CR, CR-LF
Code:
Binary (for Modbus-RTU)
ASCII (for UNI-Format)
12
Interface
B8
B9
B10
RS-485 terminal
B+
A-
SG
RS-485 signal ground terminal
Содержание F325
Страница 1: ...01JUN2015REV 1 01 DIGITAL INDICATOR F325 OPERATION MANUAL...
Страница 153: ...142 15 Specifications 142 Specifications Chapter 15 When BCO BSC option is selected Unit mm When BSC option is selected...
Страница 154: ...143 15 Specifications 143 Specifications Chapter 15 When DAV DAI option is selected Unit mm When DAI option is selected...
Страница 155: ...144 15 Specifications 144 Specifications Chapter 15 When RS 232C option is selected Unit mm...
Страница 160: ......