118
5
COMMUNICATIONS
118
COMMUNICA
TIONS
Chapter
5
- List of zero calibration commands
- List of actual load calibration commands
Input range
Actual Load Calibration (Y-axis Setting):
-9999 to 9999
Actual Load Calibration (X-axis Setting):
-9999 to 32000
Item group
Setting item
Command (transmission to the F381A)
First
Setting
Y-axis
Setting
Zero
Calibration
C
0
1
0
0
Delimiter
(CR, CR+LF)
X-axis
Setting
Zero
Calibration
C
0
2
0
0
Delimiter
(CR, CR+LF)
Note1)
Please change other set values beforehand so that the setting range
becomes the maximum when a set value to which other settings influence the
setting range is written in.
Example 1
When you write the Load HI Limit value in.
Please write -9999 in the Load LO Limit value beforehand.
Example 2
When you change the Section Start-End.
Please write 2047(Time or Displacement (Front)) and -2047(Displacement
(Back)) in at the start point and the end point in all sections beforehand in
order of End Point of Section 5, Start Point of Section 5, End Point of
Section 4,
……
End Point of Section 1 and Start Point of Section 1.
Please write in the value to be set in order of Start Point of Section 1, End
Point of Section 1, Start Point of Section 2,
……
Start Point of Section 5
and End Point of Section 5.
Point
Item group
Setting item
First
Setting
Y-axis
Setting
Actual Load
Calibration
C
0
1
0
1
X-axis
Setting
Actual Load
Calibration
C
0
2
0
1
Command (transmission to the F381A)
±
0
0
0
10
3
10
2
10
1
10
0
Delimiter
(CR, CR+LF)
±
0
0
10
4
10
3
10
2
10
1
10
0
Delimiter
(CR, CR+LF)
Содержание DeviceNet F381A
Страница 1: ...15APR2013REV 3 10 DYNAMIC FORCE PROCESSOR F381A OPERATION MANUAL ...
Страница 9: ...Contents VIII Contents VIII M E M O ...
Страница 34: ...25 2 INSTALLATION AND CONNECTION 25 INSTALLATION AND CONNECTION Chapter 2 M E M O ...
Страница 147: ...138 8 SPECIFICATIONS 138 SPECIFICATIONS Chapter 8 8 2 Outside dimensions Unit mm ...
Страница 164: ......