Sageon III Power System
Configuration and Operation
PM990-8800-00, Rev. 9
4-3
Parameter
Description
48V System
Range
48V
System
Default
User
Value
Eq End
Current
Equalization termination for I bat <
Eq End
1-2,000A
5A
Eq duration
Maximum duration of Equalization
charging
3-48Hr
20Hr
Eq period
Time between periodic Equalization
charging
0-52wk
12 Wk
Manual
Stop/Start Eq
Force stop/start of Equalization
charging
Toggle state
LVDS Trip
Battery voltage below which LVDS
will open
40-48V
42.6V
BDT Per
Period between consecutive
discharge tests
0-365 days
0 days
BDT Time
Time of day to begin BDT (hr:min) 00:00-23:59 02:00
BDT Dur
Maximum duration of BDT
5-1,440 min 180 min
BDT Curr
Discharge test current
0-5,000A
50A
BDT End V
Battery voltage limit to terminate
BDT
36-48V
44V
BDT End Q
Battery capacity limit to terminate
BDT
25-9,995AH 300AH
Temp Sen
Alarm
Enable/disable temp. sensor failure
alarm
On/Off
On
4.1 THE “HOME” SCREEN
The Home screen, shown at right, is the default screen. It shows Sageon III Power System output current and voltage. This screen also
shows the present mode: FLoat or EQualize. If an activity such as battery discharge is being
performed, the current and voltage are displayed continuously while the second line alternates
between the mode and the activity status, for example “BDT in progress.”
The Home screen is the first to appear when power is applied to the System. Since the Home screen is the default screen, the display
will revert to the Home screen from any other screen if an operator panel push button is not pressed for approximately one minute.
Section 4.5 describes in detail the selections available from the Home screen.
4.2 USING THE OPERATOR PANEL PUSH BUTTONS
Use the six buttons to view System data, individual rectifier data, battery data, or the alarm log. In addition, programmable parameter
values can be viewed and changed. Each button is described below.
The HOME screen shows the System voltage and current. The data will initially be located in the center of the display and after a brief
period will scroll right to left. From the HOME screen, press “up arrow” or “down arrow” to move through the series of menus
described in Section 4.5.
RECT
BATT
LOG
INC
DEC
ENTER
FIGURE 4-1 OPERATOR PANEL
155A 54.2
FL
Содержание Sageon III
Страница 43: ...Installation Sageon III Power System PM990 8800 00 Rev 9 2 22 FIGURE 2 20 SAGEON III BOARD LOCATIONS...
Страница 46: ...Sageon III Power System Commissioning PM990 8800 00 Rev 9 3 3 FIGURE 3 1 SINGLE PHASE FEED PHASE TO NEUTRAL...
Страница 47: ...Commissioning Sageon III Power System PM990 8800 00 Rev 9 3 4 FIGURE 3 2 SINGLE PHASE FEED PHASE TO PHASE...
Страница 50: ...Sageon III Power System Commissioning PM990 8800 00 Rev 9 3 7 FIGURE 3 5 Y THREE PHASE FEED PHASE TO NEUTRAL...