Introduction
Sageon III Power System
PM990-8800-00, Rev. 9
1-6
Immunity continues…
Immunity:
Category
Tested To
Criterion
Surge Protection
ANSI C62.41-1991 category B3 – AC lines
(Combination Wave 6 kV/3 kA; Ring Wave 6 kV/500A)
IEC 61000-4-5; EN 61000-4-5: (Impulse)
(6 kV/3 kA Common Mode [CM] on AC lines)
(6 kV/3 kA Differential Mode [DM] on AC lines)
(0.5 kV/0.25 kA CM & DM on DC lines)
IEC 61000-4-12; EN 61000-4-12: (Ring Wave)
(6 kV/500A, 100 kHz CM & DM on AC lines)
(2 kV CM, 1 kV DM on DC lines)
A
B
A
A
A
Conducted RF
IEC 61000-4-6; EN 61000-4-6
(3V on AC, load and comms lines)
A
Voltage Dip,
Interruptions
IEC 61000-4-11; EN 61000-4-11
(Level: 100% dip for 10 ms)
(Level: 30% dip for 500 ms)
(Level: 100% dropout for 5s)
B
A
B
Rectifier Specifications
FIGURE 1-3 600A PLANT
FIGURE 1-4 1200A PLANT