5.11.2 Front Panel Pushbuttons
There are six push buttons associated with the LED screen for the purpose of entering different menus
and for scrolling through the menus. The layout of the push buttons is shown below:
RECT
BATT
LOG
INC
DEC
ENTER
Apart from the base menu (system parameters), there are three other menus, which can be accessed by
momentarily pressing the relevant pushbuttons:
a)
RECT
ifier menu, which includes the rectifier related programmed parameters as well as the
output current and heat-sink temperature for each rectifier;
b)
BATT
ery menu in which all the parameters relating to the batteries are found;
c)
LOG
which stores the individual alarm event information together with date and time starting
with the most recent alarm. A total of 100 alarms are stored.
5.11.3 Status Indicating LEDs (Controller)
SYSTEM OK
Green LED
ALARM
!
Amber LED
RECTIFIER SHUTDOWN
x
Red LED
All LEDs off, indicates the unit is off due to either DC power not present, or there is an internal failure of
controller
The amber LED indicates any alarm condition, either system or rectifier related.
The red LED indicates that one or more of the rectifiers in the system is shut down.
5.12 CONTROLLER SECURITY & ALARMS
5.12.1 Password security
Controller features password security for setting of parameter. A valid password is an alphanumerical
code having minimum three and maximum eight characters.
Units leave the factory without a pre-programmed password and the security function is not active. To
activate the security, a password must be programmed. Once that is done, security can be enabled.
5.12.1.1 Entering a password to gain access to parameters change
When the security function is active any changes to the system settings can be done only after a valid
password was entered. When the ENTER key is pressed to change a parameter, the display will show a
message “Enter Password” on the top line and a blinking cursor on the right hand side of the bottom line.
Using INC and DEC keys scroll to the first character of the password and press ENTER. The character
will be substituted by an asterisk (*) displayed to the left of the cursor. Enter all characters of the
password the same way. If the password is less than eight characters long press ENTER again after last