INSTALLATION & OPERATING MANUAL

Scimitar 5000 Series

5000W 3RU RACK-MOUNT INVERTERS

Document Number: SCIMITAR5000-MAN Rev 3 

© 2020 UNIPOWER LLC

All Rights Reserved

UNIPOWER, LLC
65 Industrial Park Rd
Dunlap, TN 37327
Phone: +1-954-346-2442
Toll Free: 1-800-440-3504
Web site: 

www.unipowerco.com

Содержание INV2450R-B

Страница 1: ...ANUAL Scimitar 5000 Series 5000W 3RU RACK MOUNT INVERTERS Document Number SCIMITAR5000 MAN Rev 3 2020 UNIPOWER LLC All Rights Reserved UNIPOWER LLC 65 Industrial Park Rd Dunlap TN 37327 Phone 1 954 34...

Страница 2: ...States Manufacturing facility UNIPOWER Slovakia SRO ZLATOVSKA 1279 Business Center 22 91105 Trencin Slovakia Phone 1 954 346 2442 Toll Free 1 800 440 3504 Web site www unipowerco com When contacting...

Страница 3: ...7 2 2 Rear Panel Description 7 2 3 Installation 9 2 4 Quick Hook up and Testing 10 2 5 Safety Grounding 11 2 6 Making DC Connections 12 2 7 Alarm Connection 13 2 8 Inverter Operation 13 2 9 Cooling F...

Страница 4: ...frequency 50 60Hz switch RS 232 interface Remote controls port Wire connection to PC Wired Remote control Loading and Temperature controlled cooling fan Advanced microprocessor Protection Input Under...

Страница 5: ...switch selectable SNMP option Operates in conjunction with NetAgent UPS SNMP Agent STS Section By Pass AC Input Range 90 130VAC 110VAC nominal 180 260VAC 230VAC nominal Frequency 50 63Hz 3 Transfer Ti...

Страница 6: ...indd SCIMITAR 5000 1 74 44 25 2 70 68 5mm 1 22 31 0mm 3 46 40 0mm 19 84 504 0mm 3 94 100 0mm 5 20 3 50 0 12 3 0mm 132 0mm 88 9mm 0 12 3 0mm 18 98 482 2mm 18 31 465 1mm 1 73 1 26 18 98 482 0mm 0 12 3...

Страница 7: ...e reading associated with the actual parameter indicated by the top row of LEDs in the sequence VAC AMP WATT VDC TEMP Hz In the event of a fault condition this will be indicated on the display See sec...

Страница 8: ...ply is available to the by pass circuit NC and COM are shorted When the inverter is switched on and there is no AC supply available to the by pass circuit NO and COM are shorted When the inverter is s...

Страница 9: ...he rack environment may be greater than the room ambient consideration should be given to installing the inverter in an environment compatible with the maximum ambient temperature of 60 C 2 3 3 Safe D...

Страница 10: ...s been correctly fitted after installation or when any maintenance has taken place 2 3 16 Protection in PRIMARY CIRCUITS against over currents short circuits and earth faults shall be provided either...

Страница 11: ...et the power switch to the OFF position The unit should shut down completely 2 4 7 To accurately measure the true output R M S voltage of inverter connect to one of the outlet sockets and then set the...

Страница 12: ...be earthed elsewhere The DC supply source is to be located within the same premises as the equipment Switching or disconnecting devices shall not be in the earthed circuit conductor between the DC so...

Страница 13: ...es or wiring used for such connections must be double insulated 2 8 Inverter Operation To operate the power inverter turn it on using the ON OFF switch on the front panel The power inverter is now rea...

Страница 14: ...43 0VDC 42 0VDC 2 8 8 Over voltage protection indicator OVP When OVP is indicated on the display the unit has shut itself down due to the input voltage exceeding the limits shown above 2 8 9 Under vo...

Страница 15: ...be checked to ensure that they are sufficiently tight 4 Troubleshooting Guide WARNING Do not open or disassemble the inverter Attempting to service the unit yourself may result in a risk of electrica...

Страница 16: ...rain snow spray or dust To reduce risk of hazard do not cover or obstruct the ventilation openings Do not install the Inverter in a zero clearance compartment as overheating may result 6 1 2 To avoid...

Страница 17: ...BAUD RATE ACV ADJ ON 60 OFF OFF 2400 SCIMITAR 3000 OFF 50 OFF ON 4800 ON OFF 9600 ON ON 19200 default setting as shipped 8 Communications Protocol Remote ON OFF Function Scimitar 3000 Series inverters...

Страница 18: ...ger number ranging form 0 to 9 The unit is Volts e O P current QQQ QQQ is a percent of maximum current not an absolute value f I P frequency RR R R is an integer number ranging from 0 to 9 The unit is...

Страница 19: ...accuracies Specifications are subject to change without notice INVERTER Response 208 4 140 0 208 4 034 59 9 54 2 35 0 00110000 cr Means AC I P voltage is 208 4V SPEC AC I P fault voltage is 140 0V SPE...