4.11 Battery Installation
The batteries should be handled according to the battery manufacturer’s recommendations.
When placed into the cabinet, the recommended distance of 5-15mm between the battery
blocks should be adhered to to ensure proper ventilation.
1. Attach interblock connections between the battery blocks (Figure 4-10, Detail 1).
2. Connect the negative “-”cable to the negative pole of the battery string (Figure 4-10,
Detail 2). Tighten the connection to a torque of 5-6Nm.
3. Connect the positive “+” cable to the positive pole of the battery string (Figure 4-10,
Detail 3). Tighten the screw to 5-6Nm.
4. Attach plastic pole protection caps to the battery poles (Figure 4-10, Detail 4).
Repeat steps 1to 4 to connect the battery cables to the remaining battery strings.
NOTE
The battery installation procedure is an example and may vary depending on the
battery type.
2
1
3
4
Figure 4-10 Battery Installation (Example only)