11.0 INSTALLATION

11.1 Mounting.

  This distribution panel can be mounted in either 19- or 23-inch racks by 

using the supplied reversible brackets.  Mount it from the front of the rack using the 

correct offsets to align with existing rack-mounted equipment.  The bracket offsets 

are every quarter inch from front to back.

 

A minimum air clearance of 1.5” above and below the unit must be maintained after 
installation in the rack.  Care should be taken not to compromise the stability of the 
rack by the installation of this unit.

11.2 Connections.

  Input connections should be made with two-terminal crimp type lugs.  

See Sections 9.2 and 9.3.  

 

Connection to Supply

a)  Connect to a reliably grounded 12VDC to 48VDC SELV source.
b)  The branch circuit over-current protection shall be sized appropriate to the input 

current and shall not exceed 600A.

c)  Use minimum 350Kmcm copper conductors for max. rated input current.

d)  A readily accessible disconnect device that is suitably approved and rated is 

recommended to be incorporated in the field wiring.

e)   To be installed in a Restricted Access Location.

 

NOTE:  Single feed models DPP2U-A1-B1-S and DPP2U-A6-B6-S have both left 

and right side input bus bars fitted.  It is only necessary to connect the input feed to 

one side for correct operation.

 

The unused side is directly connected to the live input feed and can be used for 

supplying additional panels.  See figure 10 below.

 

CAUTION:

 The total load must not exceed 450A on any one pair of bus bars in the 

chain.

450A MAX. FEED

RETURN

 

Figure 10.  Series Connection of Multiple Panels

 

Output connections are made to individual output bus bars and common return. See 
Section 9.4 and Figure 6.

Содержание DPP2U Series

Страница 1: ...TRIBUTION PANELS Manual No DPP2U MAN Rev 5 UNIPOWER LLC 65 Industrial Park Rd Dunlap TN 37327 Phone 1 954 346 2442 Toll Free 1 800 440 3504 Web site www unipowerco com 2019 UNIPOWER LLC All Rights Res...

Страница 2: ...TION 4 2 0 FEATURES 4 3 0 PRODUCT LINE 5 4 0 SAFETY INDUSTRY STANDARDS 6 5 0 WARRANTY summary 6 6 0 DESCRIPTION OF OPERATION 7 7 0 SPECIFICATIONS 8 8 0 FRONT PANEL DESCRIPTION 8 9 0 BACK PANEL DESCRIP...

Страница 3: ...2U DC Power Distribution Panel 4 Figure 2 Block Diagram 7 Figure 3 Front Panel View 8 Figure 4 Back Panel View 9 Figure 5 Input Bus Bar Detail 9 Figure 6 Output Barrier Strip Detail 10 Figure 7 Alarm...

Страница 4: ...e up to 20 breakers single bus 450Aor 10A 10B 450A 450Adistribution and alarm capabilities The A and B sections of the dual bus panel are fully isolated can be separately configured for 12 or 24 48 vo...

Страница 5: ...T NUMBER 2 5 348 1441 0020 50 348 1441 0500 5 348 1441 0050 60 348 1441 0600 10 348 1441 0100 80 348 1441 0800 15 348 1441 0150 100 348 1441 1000 20 348 1441 0200 125 2 775 1524 0000 25 348 1441 0250...

Страница 6: ...this Distribution Panels the chassis ground terminal must be connected to the system frame ground or other proper safety ground for the protection of personnel 4 5 All connections to the Distribution...

Страница 7: ...CUIT BREAKERS BATT BATT INPUT RET INPUT RET HI CURRENT BUS BAR HI CURRENT BUS BAR HI CURRENT BUS BAR HI CURRENT BUS BAR LOADS LOADS 1 2 3 N A SIDE ALARM CIRCUITS B SIDE ALARM CIRCUITS A SIDE B SIDE S...

Страница 8: ...ugs Alarm Relay Connections Spring Clamp Terminals 16 26AWG Notes 1 See ordering guide to specify 8 0 FRONT PANEL DESCRIPTION The front panel of the DPP2U shown in Figure 3 below consists of the A and...

Страница 9: ...16 0 0 76 19 3 0 42 10 7 6 4 1 4 20 stud length 0 50 12 7 0 625 15 88 spacing 1 4 20 stud length 0 38 9 7 0 625 15 88 spacing 0 57 14 5 0 37 9 4 0 90 22 9 0 306 7 8 0 49 12 5 x 0 31 7 9 slot 3 50 88 9...

Страница 10: ...rear All connections use 1 4 20 threaded studs and are rated up to 100 amperes Maximum wire size is 2AWG UNIPOWER recommends using FLEX wire with either Panduit LCDXN2 14A E or LCDXN2 14AF E 90deg an...

Страница 11: ...onnection is made via two Phoenix Contact spring clamp terminal blocks J3 is for the Form C relay contact of side B and J4 is for the Form C relay contact of side B Terminals 1 2 and 3 viewed from lef...

Страница 12: ...0 57 14 5 0 37 9 4 0 90 22 9 0 306 7 8 0 49 12 5 x 0 31 7 9 slot 3 50 88 9 1 25 31 8 5 98 151 9 0 60 15 2 0 76 19 3 1 725 43 82 0 56 14 2 0 21 5 3 1 13 28 7 0 22 5 6 3 45 87 6 B B A Chassis GND 1 4 20...

Страница 13: ...here is evidence of damage do not attempt to test the unit The freight carrier should be notified immediately and a claim for the cost of the rectifier system should be filed with the carrier for dire...

Страница 14: ...eliably grounded 12VDC to 48VDC SELV source b The branch circuit over current protection shall be sized appropriate to the input current and shall not exceed 600A c Use minimum 350Kmcm copper conducto...

Страница 15: ...nput connections to the distribution panel and output connections to the load before operating the panel Reverse connections will not harm the distribution panel which is POLARITY NEUTRAL but may caus...

Страница 16: ...remove the cover plate undo the two knurled retaining screws at the left and right side of the unit and pull forward 12 2 Removing a breaker or blanking panel To remove a breaker pull the toggle swit...

Страница 17: ...l is rated for continuous operation at a maximum input of 450A per side 35C max 400A per side 40C max 320A per side 50C max and 200A per side 70C max 12 5 Connecting or disconnecting load circuits In...

Страница 18: ...n J4 measure the resistance between pins 1 and 2 This should read open Measure the resistance between pins 2 and 3 This should read short 13 5 On the A side trip circuit breaker no 1 The A side LED sh...

Страница 19: ...LLC 65 Industrial Park Rd Dunlap TN 37327 United States Manufacturing facility UNIPOWER Slovakia SRO ZLATOVSKA 1279 Business Center 22 91105 Trencin Slovakia Phone 1 954 346 2442 Toll Free 1 800 440...

Отзывы: