Page 10

DPP2U SERIES

OPERATING MANUAL

P O W E R I N G   T E C H N O L O G Y

Manual No. DPP2U-MAN Rev. 5

dpp2u-man-rev5-0719.indd

9.3 

Recommended Input Cable Sizes and Lugs

The following table details the recommended cable size for various input current.

MAXIMUM

CURRENT

CONDUCTOR

SIZE

PANDUIT CORP.

PART NUMBER

TORQUE

1/4 x 20 BOLT

450A

350KCMIL

LCC350-14BW-X

62 in-lbs

400A

300KCMIL

LCCX250-14B-X

62 in-lbs

320A

4/0 AWG

LCCX4/0-14B-X

62 in-lbs

200A

 3/0 AWG

LCCX3/0-14B-X

62 in-lbs

150A

1/0 AWG

LCCX1/0-14B-X

62 in-lbs

9.4 

Output Connections.  

Output connections for A and B loads are shown in Figure 4. 

There are 10 sets of bus bar terminals for each side, A and B.  The connections are 
numbered to correspond with the numbers of the front panel breakers.  The upper 
strip connections are from the battery (FEED) through the breakers; the lower strip 
connections are the RETURNS.  Side B is on the left and side A on the right when 
viewed from the rear.  

 

All connections use 1/4-20 threaded studs and are rated up to 100 amperes. Maximum 

wire size is 2 AWG.  UNIPOWER  recommends using FLEX wire with either Panduit 
LCDXN2-14A-E or LCDXN2-14AF-E (90deg angle) lugs.  When 125A, 150A or 
200A breakers are installed two positions are utilized.  Figure 6 below shows detailed 
spacing of the terminals.

A - ALM

B - ALM

1

2

3

4

5

6

7

8

9

10

A BUS - 450A MAX/100A MAX PER CB

1

2

3

4

5

6

7

8

9

10

B BUS - 450A MAX/100A MAX PER CB

NO-C-NC  NO-C-NC

ALM-B

ALM-A

NO-C-NC  NO-C-NC

10

9

8

7

6

5

4

3

2

1

0.63

(16.0)

0.76

(19.3)

0.42

(10.7)

0.25
(6.4)

1/4-20 stud
length = 0.50 (12.7),
0.625 (15.88) spacing

1/4-20 stud

length = 0.38 (9.7),

0.625 (15.88) spacing

0.57

(14.5)

0.37
(9.4)

0.90

(22.9)

ø

 0.306 (7.8)

0.49 (12.5) x

0.31 (7.9) slot

3.50

(88.9)

1.25

(31.8)

5.98

(151.9)

0.60

(15.2)

17.16

(435.9)

0.76

(19.3)

1.725

(43.82)

0.56

(14.2)

0.21
(5.3)

1.13

(28.7)

0.22
(5.6)

3.45

(87.6)

A - BUS OUTPUT FEED

B - BUS OUTPUT FEED

A - BUS RETURN

B - BUS RETURN

B - BUS FEED BREAKERS

A - BUS FEED BREAKERS

Alarm connector

Chassis GND

(1/4-20 THREAD)

A - BUS INPUT

FEED

B - BUS INPUT

FEED

10

9

8

7

6

5

4

3

2

1

Shorting Bus (-S Models)

OUTLINE OF SAFETY COVER

(blue dotted line)

4.60

(116.8)

0.625

(15.88)

0.500

(12.70)

0.750

(19.05)

4.642

(117.91)

Figure 6.  Output Barrier Strip Detail

 

The following table lists a range of cable sizes with matching lugs that will fit the 

output terminals.  The indicated current rating is the maximum assuming that the 

cables are bundled/confined.

Содержание DPP2U Series

Страница 1: ...TRIBUTION PANELS Manual No DPP2U MAN Rev 5 UNIPOWER LLC 65 Industrial Park Rd Dunlap TN 37327 Phone 1 954 346 2442 Toll Free 1 800 440 3504 Web site www unipowerco com 2019 UNIPOWER LLC All Rights Res...

Страница 2: ...TION 4 2 0 FEATURES 4 3 0 PRODUCT LINE 5 4 0 SAFETY INDUSTRY STANDARDS 6 5 0 WARRANTY summary 6 6 0 DESCRIPTION OF OPERATION 7 7 0 SPECIFICATIONS 8 8 0 FRONT PANEL DESCRIPTION 8 9 0 BACK PANEL DESCRIP...

Страница 3: ...2U DC Power Distribution Panel 4 Figure 2 Block Diagram 7 Figure 3 Front Panel View 8 Figure 4 Back Panel View 9 Figure 5 Input Bus Bar Detail 9 Figure 6 Output Barrier Strip Detail 10 Figure 7 Alarm...

Страница 4: ...e up to 20 breakers single bus 450Aor 10A 10B 450A 450Adistribution and alarm capabilities The A and B sections of the dual bus panel are fully isolated can be separately configured for 12 or 24 48 vo...

Страница 5: ...T NUMBER 2 5 348 1441 0020 50 348 1441 0500 5 348 1441 0050 60 348 1441 0600 10 348 1441 0100 80 348 1441 0800 15 348 1441 0150 100 348 1441 1000 20 348 1441 0200 125 2 775 1524 0000 25 348 1441 0250...

Страница 6: ...this Distribution Panels the chassis ground terminal must be connected to the system frame ground or other proper safety ground for the protection of personnel 4 5 All connections to the Distribution...

Страница 7: ...CUIT BREAKERS BATT BATT INPUT RET INPUT RET HI CURRENT BUS BAR HI CURRENT BUS BAR HI CURRENT BUS BAR HI CURRENT BUS BAR LOADS LOADS 1 2 3 N A SIDE ALARM CIRCUITS B SIDE ALARM CIRCUITS A SIDE B SIDE S...

Страница 8: ...ugs Alarm Relay Connections Spring Clamp Terminals 16 26AWG Notes 1 See ordering guide to specify 8 0 FRONT PANEL DESCRIPTION The front panel of the DPP2U shown in Figure 3 below consists of the A and...

Страница 9: ...16 0 0 76 19 3 0 42 10 7 6 4 1 4 20 stud length 0 50 12 7 0 625 15 88 spacing 1 4 20 stud length 0 38 9 7 0 625 15 88 spacing 0 57 14 5 0 37 9 4 0 90 22 9 0 306 7 8 0 49 12 5 x 0 31 7 9 slot 3 50 88 9...

Страница 10: ...rear All connections use 1 4 20 threaded studs and are rated up to 100 amperes Maximum wire size is 2AWG UNIPOWER recommends using FLEX wire with either Panduit LCDXN2 14A E or LCDXN2 14AF E 90deg an...

Страница 11: ...onnection is made via two Phoenix Contact spring clamp terminal blocks J3 is for the Form C relay contact of side B and J4 is for the Form C relay contact of side B Terminals 1 2 and 3 viewed from lef...

Страница 12: ...0 57 14 5 0 37 9 4 0 90 22 9 0 306 7 8 0 49 12 5 x 0 31 7 9 slot 3 50 88 9 1 25 31 8 5 98 151 9 0 60 15 2 0 76 19 3 1 725 43 82 0 56 14 2 0 21 5 3 1 13 28 7 0 22 5 6 3 45 87 6 B B A Chassis GND 1 4 20...

Страница 13: ...here is evidence of damage do not attempt to test the unit The freight carrier should be notified immediately and a claim for the cost of the rectifier system should be filed with the carrier for dire...

Страница 14: ...eliably grounded 12VDC to 48VDC SELV source b The branch circuit over current protection shall be sized appropriate to the input current and shall not exceed 600A c Use minimum 350Kmcm copper conducto...

Страница 15: ...nput connections to the distribution panel and output connections to the load before operating the panel Reverse connections will not harm the distribution panel which is POLARITY NEUTRAL but may caus...

Страница 16: ...remove the cover plate undo the two knurled retaining screws at the left and right side of the unit and pull forward 12 2 Removing a breaker or blanking panel To remove a breaker pull the toggle swit...

Страница 17: ...l is rated for continuous operation at a maximum input of 450A per side 35C max 400A per side 40C max 320A per side 50C max and 200A per side 70C max 12 5 Connecting or disconnecting load circuits In...

Страница 18: ...n J4 measure the resistance between pins 1 and 2 This should read open Measure the resistance between pins 2 and 3 This should read short 13 5 On the A side trip circuit breaker no 1 The A side LED sh...

Страница 19: ...LLC 65 Industrial Park Rd Dunlap TN 37327 United States Manufacturing facility UNIPOWER Slovakia SRO ZLATOVSKA 1279 Business Center 22 91105 Trencin Slovakia Phone 1 954 346 2442 Toll Free 1 800 440...