UniPOS Duct Smoke Detector
УКВ
-02
UniPOS Duct Smoke Detector
УКВ
-02
Passport page 2
Revision 01.10 of 4
Passport page 3
Revision 01.10 of 4
Any disassembly of the duct smoke detector from the main air conduit is
inadmissible except it is switched off.
4
. Mount the device on the air conduit by the six self-tapping screws from the set,
and put the duct smoke detector in position so that the inlet tube holes (pos.7, Fig.
4) (poz.8, Fig.4) are upstream (poz.11, Fig.4) the air flow.
Repairing
is not allowed while the Fire Control Panel is plugged in the power
supply.
5
. Unscrew the 8 screws (pos.1, Fig.4) and remove the lid (pos.2, Fig.4) of the
body (pos.5, Fig. 4) of the duct smoke detector.
INSTALLATION
1.
On mechanical and electrical assemblage
of the device common iinstructions for fire
detector mountage in firealarm lines
(loops)should be followed.
2
. There is possibility for the duct smoke
detector to be situated on the side, on top, or
below the air conduit only in case all the
instructions have been observed.
-inlet tube holes (pos.7, Fig.4) are facing the
80
186
135
22
Fig.2
Note
: Removing the lid must be made with caution since the Remote indicator
(pos.3, Fig.4) is factory built-in together with the fire detector base.
Removing the lid provides access to the optical smoke fire detector.mounted in the
duct smoke detector.
6
Take-off the fire detector (pos.4, Figure 4) from the base.
7
. Lead the wires of the fire alarm line (loop) through the input and output
nozzles (pos.10, Fig.4) of the duct smoke detector.
8.
Connect the wires to the base:
(Remote Indicator Rl31 (pos.3, Fig.4) is
factory built-in with the detestor base)
- for Conventional Control Panel (Fig.5).
air flow (pos.11, Fig 4 );
-visibility distance of the light-emitting
diode(LED) of the Remote Indicator
3.
Drill mounting holes on a preliminary
specified project location of the air duct
according to the dimensions Figure 2.
On
t
he inlet and outlet tubes place rubber
sealing washers from the set.
Ai
r f
lo
w
Inlet t
u
be
Outlet t
u
be
Air conduit
+
Fig.5
Sealing
- for Addressable Control Panel (Fig.6)
Fig.3
1. Mounting Screw
2. Duct Detector Cover
3. Remote indicator
4. Optical-smoke fire detector
5. Duct Detector Housing
6. Holes for mountage on air conduit
7. Inlet tube holes
8. Inlet tube
9. Outlet tube
10. Nozzles
11. Airflow
1
2
3
4
5
6
7
8
9
10
+
Fig.6
9
. Put the fire detector to its base.
10
. Place the lid (position2, Figure 4) of the device and bolt up the screws (pos.1,
Figure 4).
COMPLEXITY
•
Duct Smoke Detector with components assembled: - 1 pc
- Outboard Remote Indicators RI31;
- Detector Base DB8000D ( DB7100 );
- Optical-smoke fire detector FD 8030 ( FD7130 )
•
Instruction Manual
- 1 pc
11
•
Self-tapping screws
- 6 pcs
Fig.4
•
Sealing
- 1 pc
•
Transport package
- 1 pc