UniPOS
Interactive Fire ControlPanel IFS7002
Instruction Manual
Page
50
Revision 2.05
Of 107
−
If disabled addressable
output modules are available
– the first disabled
addressable output module
will be displayed, and the text
message for the device will
appear in the panel bottom
section:
Buttons
and
seen in the
right panel section allow the user to
switch between the next and the
previous disabled addressable output
module (if any).
Using the digit buttons you may
enter in the
Go to
field a random 3-
digit address for the module in the
loop. To edit the number press
button
and the last entered digit will be deleted.
When you press button
after a number is entered in the
Go to
field, the status of the
addressable output module whose number is selected, will be displayed:
−
If the selected number is 0, the status of Device 1 will be displayed;
−
If the selected number is higher than 125, the status of Device 125 will be displayed.
Simultaneously, the number in the
Go to
field will be deleted; i.e. the field is deactivated.
When you press button
the addressable output module status is being changed
alternatively from
DISABLED
to
ENABLED
and reverse; in the panel bottom left section appears a
reminder
Data not saved
. Changes (disable/enable addressable output module) are accepted if you
press button
and the
Go to
field is empty – then the reminder
Data not saved
disappears.
12.3.2. Menu
Zones in Test
The menu is used to enable or disable test operation in fire alarm zones. Enter the menu to
display one of the two screens:
−
If no zones in test are
available:
Mode:DAY
15:09:10
Mon 21 Mar 2005
FIRE CONTROL PANEL IFS7002
UniPOS
Faults total: 00000
Disables total: 003
Failed Outputs: 00000
Disabled outputs: 001
System functions/Disables/Devices
Go to:
Disabled Outputs - total Loop1 002
Loop 1
OUTPUT: 005
DISABLED
Point 1.005
0
1
2
3
4
5
6
7
8
9
С
Mode:DAY
15:19:22
Mon 21 Mar 2005
FIRE CONTROL PANEL IFS7002
UniPOS
System functions/Test/Zones
Go to:
Zones in test - total 000
ZONE:
0
1
2
3
4
5
6
7
8
9
:
С