If wrong password is entered, when you press button
the digits will be deleted and the
cursor will move back to the first position. If one of the 10 passwords for Access Level 2 or Access
Level 3 is entered, when you press button
the menu will become active.
12.3.1. Menu
Disables
The menu is provided for disabling fire alarm zones, addressable devices and monitored outputs
of the control panel. It contains the following subordinate menus:
−
Menu
Zones
– provided for disabling fire alarm zones;
−
Menu
Devices
– provided for disabling addressable fire detectors;
−
Menu
Outputs
– provided for disabling outputs – monitored outputs and addressable output
modules.
12.3.1.1. Menu
Zones
Enter the menu to disable or enable fire alarm zones. Two screens are available here:
−
If no disabled zones are
available:
−
If disabled zones are
available – the first disabled
zone is displayed, and in the
bottom section of the panel
appears text message for the
zone:
Buttons
and
in the right
panel section allow the user to switch
between the next disabled zone and
the previous disabled zone (if any).
Using the digit buttons you may
enter in the
Go to
field a random 3-
digit number for a fire alarm zone. To
edit the number press button
,
and the last entered digit will be
deleted.
When you press button
after a number is entered in the
Go
to field, the status of the zone
whose number is selected will be displayed:
−
If the selected number is 0, the status of Fire alarm zone 1 will be displayed;
С
Mode:DAY
16:41:18
Fri 18 Mar 2005
FIRE CONTROL PANEL IFS7002
UniPOS
Faults total: 00000
Disables total: 003
Failed Outputs: 00000
Disabled outputs: 001
System functions/Disables/Zones
Go to:
Disabled Zones - total 002
ZONE: 001
DISABLED
Zone 001
0
1
2
3
4
5
6
7
8
9
С
Mode:DAY
16:41:18
Fri 18 Mar 2005
FIRE AALRM PANEL IFS7002
UniPOS
System functions/Disables/Zones
Go to:
Disabled Zones – total 000
ZONE:
0
1
2
3
4
5
6
7
8
9
С