UniPOS Fire Extinguishing Control Panel FS5200E
Service Personnel’s Instruction Manual page1/2
Service Personnel’s Instruction Manual for Operating
Fire Extinguishing Control Panel FS5200E
1. Indications and Buttons
1 Indicator
Hold extinguishing
2 Indicator
Fault in a circuit of signal wires
3 Indicator
System Error
4 Indicator
Fault in power supply
5 Common
Indicator
Fault Condition
6 Indicator
Manual Mode
7 Indicator
Power Supply
8 Indicator
Disabled Component
9 Indicator
Low Pressure
10
LCD display (4
х
20)
11 Indicator
Automatic Mode
12 Indicator
Fire condition stage II – Extinguishing
13 Switch
–
Automatic / Manual / Disable
14 Indicator
Fire condition stage I
15
Individual indicators of the Fire detecting lines
16 Indicator
Disable extinguishing
17 Button
Reset
18 Button
Menu
19 Button
Down
20 Button
Alarm
with indicator
Stop alarm
21 Button
Up
22 Button
Outputs
with indicator
Suppressed outputs
23 Switch
–
Access level
24 Button
Cancel
1 2 3
1 2 3
4 5 6
7
8
9
10
11
12
13 14
15
16 17
19 20
22
24
23
21
18
Fig.1
2. Duty Mode
This is the condition when the fire alarming installation is not in Extinguishing Mode, Fire condition and Fault
condition. In Duty Mode only the green LED indicator is activated
(Power supply) and the yellow indicator
for Manual Mode or
Manual Automatic Mode. The local sounder is off. The display shows a message “Fire
Protect” and information about the current local time.
3. Operation of the personnel on duty in the case of signal for Fault condition
If any fault condition is registered the sounder of the fire extinguishing control panel produces discontinuous sound
signal.
•
To stop the sound signal, turn by means of the key the switch (Pos. 23) to position
and press button.
. The LED indicator of the button starts to illuminate and the sounder stops.
•
If the indicators
and
are lit and a text message “Fault Mains Supply” is displayed check if the
voltage in the electric board supplying the fire extinguishing control panel is 220 V. If the voltage is restored
the light indications for fault condition are switched off.
•
Turn the switch to position
.
In all other cases when a fault condition is signaled, turn the switch to position
, press the button
to stop the sound signaling and call the service company.