background image

POINT

 

 FIRE

 

 DETECTOR

OPTICAL-SMOKE

TYPE

 

FD 8030

INSTRUCTION MANUAL 02-

803

0

1293

Manufactur

er: UniPOS Ltd. 114 Grenaderska Street, Pleven 5800, R. Bulgaria, http://www.unipos-bg.com

TECHNICAL DATA

Supply voltage

(10-30) VDC

Current consumption in Duty Mode

not more than 120 µA

Current consumption in Fire Condition
- with base type 8000 or 8000D

8mA/10VDC; 25mA/30VDC

- with base type 8000R, 8000DR or 8000L

18mA/10VDC; 55mA/30VDC

Smoke sensitivity

complies with EN 54-7:2000+ A1:2002

Time 

to enter

 Duty mode 

after power supply is on

up to 40s

Reset time

2

s

Time 

to enter Duty mode

 after reset

up to 40s

Protected area

circle with diameter 15 m

Height of mounting

up to 11 m

Output in Fire Condition (RI/KL terminal)

for RI 31

 or 

RI 31S

Degree of Protection

IP 43

Operational temperature range

minus 10°C - plus 55°C

Relative humidity resistance

(93±3)% at 40°C

Dimensions, base included

Ø100 mm, h 47mm

Weight, base included

0,100 kg

Type of connecting cable

two-wire

2

Cross section

 of the con

necting wire

(0,8-2,5) mm

INSTALLATION

  

 

The fire detector operates with bases type 

8000

 (standard), 

8000D

 (with Schottki diode), 

8000R

 (with relay 

output)

,

 

8000DR

 (with Schottki diode and resistor 510 

Ù)

 or 

8000L

 (with resistor 510 

Ù)

. They are delivered 

separately  and  are  fixed  on  the  desired  place  in  advance  by  means  of  pins  and  screws.  The  electrical 
connection of the components necessary for the installation is done according to the schematic diagram on 

fig.2

. It is recommended cable shoes to be used.

 

  The fire detector is placed on the base (fig.1,pos.1). It is rotated clockwise until reaching the guiding grooves 

(fig.1,pos.2). It is rotated until rest (fig.3.1). The slots of the base and the bo

dy

 should match (fig.3.2).

Locking of the fire detector (fig.4).

 Before installation, the key (pos.3) is detached from the base and the rib 

(pos.1) of the locking click 

(pos.2) 

is cut out.

Removing of a fire detector locked to the base.

 Insert the key into the slot (pos.4) push in as in the same 

time the fire detector is rotated anticlockwise. Remove the key and continue to rotate the fire detector in the 
same direction until it is released from the base.

TESTING

 

   The fire detector is tested after installation as a part of the site's fire alarm system or 

with

 maintenance 

activities, following this order:
1.Voltage is supplied to the fire alarm line, to which the tested fire detector is connected, from the Fire Control 
Panel or auxiliary power supply unit 24V

 

DC/0,1A.

2.After one minute is activated the fire detector using a 

Smoke Detector

 

T

ester. It should enter Fire condition 

within 

4

0s.

3.Within 2s is interrupted the supply voltage to the fire alarm line, to which the tested fire detector is connected 
or a reset command is sent from the Fire Control Panel. Fire detector should enter Duty mode and is ready for 
a new activation within 40s.

SERVICE SCHEDULE

 

 

  

It

 i

done

 by authorized person

nel

 and 

includes

 the f

o

llow

ing

 activities:

1.Inspection for visible physical damage

- monthly

2.

T

est

ing

 in real conditions

- monthly

3.*Preventive cleaning of the optic chamber

- every 6 months

*

The fire detector is removed from the base. The body cover (fig.1,pos.6) is removed

 by rotating to rest 

anticlockwise

.

 

T

he optic chamber cover (fig.1,pos.7) and the screen (fig.1,pos.8)

 are removed

. For the optic 

chamber cover and the screen it is permitted washing liquid to be used. Then they should be rinsed out and 
dried.

 

The optic chamber is dusted with a small brush. 

The optic chamber is compulsory dusted when the 

fire detector enters Contaminated chamber Mode.

 If it is not cleaned in due time it will get contaminated to 

such an extent that it would not allow the proper functioning of the fire detector which will be signaled as Fire 
Condition.

WARRANTY

   

The warranty period is 36 months from the date of sale.

  

The manufacturer

 

guarantees the normal operation of the fire detector providing that the requirements set 

herein have been observed.

   

The manufacturer does not bear warranty liabilities for damages caused through accidental mechanical 

damage, misuse, adaptation or modification after production. The manufacturer bears warranty liabilities for 
damages in the fire detector caused through manufacturer's fault only.

GENERAL DESCRIPTION

 

 The fire detector is designed for early warning of a fire condition responding to fixed threshold smoke 

concentration detected in the protected premises. The smoke sensitivity is factory preset. The principle of 
functioning of the detector is based on infrared rays distraction caused by smoke particles entering the optic 
chamber. The fire detector is controlled by a microprocessor, operating on the basis of improved algorithm for 
self-compensation of the chamber contamination.

 

 The fire detector 

(fig.1)

 consists of 

printed circuit board and an optic chamber (pos.4), fixed in a plastic 

body (ïîç.5).

 

 

 

Both LED indicators (pos.3) allow range of visibility 360° and provide information for the status:

-Duty mode

 - the LEDs are not lit;

-Fire condition

 - the LEDs produce continuous light;

-Contaminated chamber

 - the LEDs flash briefly every 1s.

051-5

All manuals and user guides at all-guides.com

all-guides.com