CONVENTIONAL LINE-MONITORING

 MOD

ULE

T

ype

 

FD 7

20

1S

Instruction Manual 01-7201S-

11

-0

5

Producer: UniPOS Ltd. 114 Grenaderska Street, Pleven 5800, Bulgaria, http://www.unipos-bg.com

INSTALLATION

    

To install the module please follow the sequence:

   

1.Remove the cover  (fig.

1

 pos.

3

) by unscrewing the fixings (fig.

1

 pos.

7

).

   

2.Remove the frame (fig.

1

pos.

4

) from the base by unscrewing the fixing (fig.

1

 pos.

5

).

   

3.Puncture the installation holes and the cable entries on the bottom of the base, observing the markings. 

   

4.Fix the base at the desired point of the protected area using appropriate fixings. If necessary,  feed the cables 

to the inside part of the body prior installation. 

   

5.Fix the frame with the printed circuit board to the base using the fixings(fig.

1

 pos.

5

).

   

6.Feed the connection wires to the conventional line-monitoring module and plant the terminating component 

on the base of the last fire detector in the conventional line, according to the electrical connection diagram, fig. 

3

Note

:  We recommend you to install diodes on the bases of all conventional fire detectors. Otherwise in case of a 

removed conventional detector the module will indicate break in the conventional line

TESTING THE CONVENTIONAL LINE-MONITORING MODULE

   

Test the module with conventional detectors connected, and after connecting the module to fire control 

panel type IFS7002 as a part of the site's fire alarm system.

   

1. Set the control panel to Duty mode. The conventional line-monitoring module shall enter Duty mode. 

   

2. Set

 twice

 any detector connected to the module's conventional line, to Fire condition. The module shall 

indicate the condition accordingly, as described above.

   

3. Send a reset command from the fire control panel IFS7002 to the conventional line-monitoring module 

FD7201S. The module shall restore the Duty Mode.

SECRIVE SCHEDULE

1. Inspection for visible physical damage

- weekly

2. Satisfactory operation test in real conditions

- monthly

WARRANTY

       The warrant period is 36 months from the date of purchase. The manufacturer guarantees the normal 
operation of the module providing that the requirements set herein have been observed. The manufacturer 
does  not  bear  warranty  liabilities  for  damages  caused  through  accidental  mechanical  damage,  misuse, 
adaptation or modification after production. The manufacturer bears warranty liabilities for damages in the 
module caused through manufacturer's fault only

.

GENERAL DESCRIPTION

   

Conventional line-monitoring module type 7201S is designed to connect up to 32 conventional fire detectors to 

an addressable fire alarm control system type IFS7000.

   

Fire control panel IFS7002 is able to exchange data with the module through a specialized communication 

protocol UniTALK, using its signal loop. The module is power supplied via the power loop and the signal loop, 
simultaneously.

   

The conventional line-monitoring module FD7201S has two built-in short circuit isolators – one for the power 

loop and one for the signal loop. 
The unit comprises a printed circuit board (fig.

1

   pos.

2

) and a frame (fig.

1

 pos.

4

) placed in a plastic body (fig.

1

       

pos.

1

).  Terminals  for  connection  to  the  signal  loop   

SL 

(fig.

2

pos.

1

),    power  loop 

PL

  (fig.

2

  pos.

3

)    and  for 

conventional detectors line

 CL

 (fig.

2

 pos.

2

) are provided on the printed circuit board. The module is completed 

with a terminating component 

EOL-2

 having a red 

R

 and a black 

B

 leads (fig.

pos.

4

) that shall terminate the 

conventional fire alarm line. 
Both LEDs (fig.

1

 pos.

6

 ) situated on the body of the module provide information for the following:

Duty mode

 - both LEDs flash every 16 seconds;

Activated short circuit isolator for the signal and/or power loop

 – the red LED is extinguished; the yellow 

LED flashes repeatedly 

every

 1 sec;

Fire detector in the conventional line in Fire condition

 – the red LED produces continuous light, the yellow 

LED is extinguished;

Removed fire detector in the conventional line

 - the red LED is extinguished; the yellow LED produces double 

flashing light, repeatedly

 every

 1 sec;

Short  circuit  or  break  in  the  conventional  line 

-  the  red  LED  is  extinguished;  the  yellow  LED  produces 

continuous light.

TECHNICAL DATA

Supply voltage:

- signal loop

(15-30)V DC

- power supply loop

(12-34)V DC

Current in Duty mode:

- signal loop

300 

µ

А at 24 VDC

- power supply loop

(

2

-

6

) mA 

Current in Fire condition:

- signal loop

3 mA at 24 VDC

- power supply loop

(

10

-

5

0) mА

Voltage of the conventional fire alarm line

(12-34)V DC

Current of the conventional line when registered:

- Break in a line

(

0-2

 mA , 

- Duty mode

(

2

-

10

) mA

- Fire condition 

(

10

-

5

0) mА

- Short circuit

higher than 

5

0 mA

2

Maximum cross-section of the connecting wires

2,5 mm

Type of the connecting wires

- signal loop

two-wire, shielded

- power supply loop

two-wire

- conventional fire alarm line

two-wire

Degree of protection

IP 50

Operational temperature range

minus 10

º

С - plus 70

º

С

Relative humidity resistance

(93 

±

3)% at 40

º

С

Dimensions 

114х79х58 mm

Weight

0,200 kg 

1293

051-2