CONVENTIONAL LINE-MONITORING
MOD
ULE
T
ype
FD 7
20
1S
Instruction Manual 01-7201S-
11
-0
5
Producer: UniPOS Ltd. 114 Grenaderska Street, Pleven 5800, Bulgaria, http://www.unipos-bg.com
INSTALLATION
To install the module please follow the sequence:
1.Remove the cover (fig.
1
pos.
3
) by unscrewing the fixings (fig.
1
pos.
7
).
2.Remove the frame (fig.
1
pos.
4
) from the base by unscrewing the fixing (fig.
1
pos.
5
).
3.Puncture the installation holes and the cable entries on the bottom of the base, observing the markings.
4.Fix the base at the desired point of the protected area using appropriate fixings. If necessary, feed the cables
to the inside part of the body prior installation.
5.Fix the frame with the printed circuit board to the base using the fixings(fig.
1
pos.
5
).
6.Feed the connection wires to the conventional line-monitoring module and plant the terminating component
on the base of the last fire detector in the conventional line, according to the electrical connection diagram, fig.
3
Note
: We recommend you to install diodes on the bases of all conventional fire detectors. Otherwise in case of a
removed conventional detector the module will indicate break in the conventional line
TESTING THE CONVENTIONAL LINE-MONITORING MODULE
Test the module with conventional detectors connected, and after connecting the module to fire control
panel type IFS7002 as a part of the site's fire alarm system.
1. Set the control panel to Duty mode. The conventional line-monitoring module shall enter Duty mode.
2. Set
twice
any detector connected to the module's conventional line, to Fire condition. The module shall
indicate the condition accordingly, as described above.
3. Send a reset command from the fire control panel IFS7002 to the conventional line-monitoring module
FD7201S. The module shall restore the Duty Mode.
SECRIVE SCHEDULE
1. Inspection for visible physical damage
- weekly
2. Satisfactory operation test in real conditions
- monthly
WARRANTY
The warrant period is 36 months from the date of purchase. The manufacturer guarantees the normal
operation of the module providing that the requirements set herein have been observed. The manufacturer
does not bear warranty liabilities for damages caused through accidental mechanical damage, misuse,
adaptation or modification after production. The manufacturer bears warranty liabilities for damages in the
module caused through manufacturer's fault only
.
GENERAL DESCRIPTION
Conventional line-monitoring module type 7201S is designed to connect up to 32 conventional fire detectors to
an addressable fire alarm control system type IFS7000.
Fire control panel IFS7002 is able to exchange data with the module through a specialized communication
protocol UniTALK, using its signal loop. The module is power supplied via the power loop and the signal loop,
simultaneously.
The conventional line-monitoring module FD7201S has two built-in short circuit isolators – one for the power
loop and one for the signal loop.
The unit comprises a printed circuit board (fig.
1
pos.
2
) and a frame (fig.
1
pos.
4
) placed in a plastic body (fig.
1
pos.
1
). Terminals for connection to the signal loop
SL
(fig.
2
pos.
1
), power loop
PL
(fig.
2
pos.
3
) and for
conventional detectors line
CL
(fig.
2
pos.
2
) are provided on the printed circuit board. The module is completed
with a terminating component
EOL-2
having a red
R
and a black
B
leads (fig.
2
pos.
4
) that shall terminate the
conventional fire alarm line.
Both LEDs (fig.
1
pos.
6
) situated on the body of the module provide information for the following:
Duty mode
- both LEDs flash every 16 seconds;
Activated short circuit isolator for the signal and/or power loop
– the red LED is extinguished; the yellow
LED flashes repeatedly
every
1 sec;
Fire detector in the conventional line in Fire condition
– the red LED produces continuous light, the yellow
LED is extinguished;
Removed fire detector in the conventional line
- the red LED is extinguished; the yellow LED produces double
flashing light, repeatedly
every
1 sec;
Short circuit or break in the conventional line
- the red LED is extinguished; the yellow LED produces
continuous light.
TECHNICAL DATA
Supply voltage:
- signal loop
(15-30)V DC
- power supply loop
(12-34)V DC
Current in Duty mode:
- signal loop
300
µ
А at 24 VDC
- power supply loop
(
2
-
6
) mA
Current in Fire condition:
- signal loop
3 mA at 24 VDC
- power supply loop
(
10
-
5
0) mА
Voltage of the conventional fire alarm line
(12-34)V DC
Current of the conventional line when registered:
- Break in a line
(
0-2
mA ,
- Duty mode
(
2
-
10
) mA
- Fire condition
(
10
-
5
0) mА
- Short circuit
higher than
5
0 mA
2
Maximum cross-section of the connecting wires
2,5 mm
Type of the connecting wires
- signal loop
two-wire, shielded
- power supply loop
two-wire
- conventional fire alarm line
two-wire
Degree of protection
IP 50
Operational temperature range
minus 10
º
С - plus 70
º
С
Relative humidity resistance
(93
±
3)% at 40
º
С
Dimensions
114х79х58 mm
Weight
0,200 kg