SERVICE

 

SCHEDULE

 

Table

 

1

 

 

Task

 

Periodicity

 

1.

 

Inspection

 

for

 

visible

 

physical

 

damage

 

weekly

 

2.

 

Satisfactory

 

operation

 

test

  

monthly

 

3.

 

Check

 

and

 

clean

 

dust

 

contamination

 

every

 

6

 

months

  

4.

 

Check

 

and

 

clean

 

base

 

and

 

head

 

contacts

 

and

 

connections

 

Annually

  

 

6.

 

WARRANTY

 

 

The

 

manufacturer

 

guarantees

 

product

 

compliance

 

with

 

the

 

EN

 

54-7:2001.

 

The

 

warrant

 

period

 

is

 

36

 

months

 

from

 

the

 

date

 

of

 

purchase,

 

providing

 

that

 

requirements

 

covered

 

in

 

section

 

5

 

have

 

been

 

observed.

 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

UniPOS

 

Ltd

 

 

SHORT

 

CIRCUIT

 

ISOLATOR

  

6202L

 

 
 
 

 

 
 

 

1.

 

INTRODUCTION

 

Short

 

circuit

 

isolator

 

6202L

 

is

 

designed

 

to

 

cut

 

off

 

(to

 

isolate)

 

a

 

short

 

circuited

 

segment

 

in

 

a

 

line

 

(loop).

 

In

 

this

 

way

 

the

 

variable

 

units

 

ñ

 

automatic

 

fire

 

detectors,

 

manual

 

call

 

points

 

and

 

others,

 

which

 

are

 

not

 

in

 

the

 

short

 

circuited

 

segment

 

remain

 

active

 

and

 

the

 

line

 

(loop)

 

protection

 

level

 

is

 

higher.

 

Where

 

isolators

 

are

 

not

 

included,

 

in

 

case

 

of

 

a

 

short

 

circuit

 

the

 

fire

 

control

 

panel

 

interrupts

 

the

 

power

 

supply

 

of

 

the

 

line

 

(loop)

 

and

 

all

 

units

 

stop

 

working.

 

A

 

segment

 

is

 

a

 

part

 

of

 

a

 

loop

 

between

 

two

 

adjacent

 

isolators.

  

 

2.

 

TECHNICAL

 

DATA

 

2.1.

 

Supply

 

voltage

 

-

 

(18

 

-

 

26)V

 

DC

 

2.2.

 

Current

 

consumption

 

in

 

quiescent

 

state,

 

at

 

26

 

V

 

DC

 

-

 

not

 

more

 

than

 

100

 

µ

A

 

2.3

.

 

Equivalent

 

resistance

 

of

 

isolator

 

in

 

a

 

line:

 

 

  

 

-

 

in

 

quiescent

 

state

 

-

 

<

 

1

 

  

-

 

in

 

alarm

 

state

 

-

 

>

 

6,5

 

k

 

  

 

2.4.

 

Connection

 

to

 

fire

 

control

 

panel

 

-

 

two-

 

wire

  

 

2.5.

 

Degree

 

of

 

protection

 

-

 

IP40

  

 

2.6.

 

Operating

  

temperature

 

range

 

-

 

minus

 

10

°

—/

 

plus

 

60

°

 

 

2.7.

 

Temperature

 

limits

 

-

 

minus

 

40

°

—/

 

plus

 

70

°

 

 

2.8.

 

Relative

 

humidity

 

resistance

 

-

 

(92

+3

 

-2

)%

 

at

  

25

°

 