APPENDIX: COMPONENTS CHARACTERISTICS

26

LANDIS LMG21/22/25 FLAME CONTROLLER

FEATURES

The series of equipment LMG.. is interchangeable with the series
LGB.., all diagrams and accessories are interchangeable, the main
features are:

Protection against overvoltage:
with voltages lower than160V ~ (with input 230V ~) the equipment
stops, when the voltage overcome 195V ~ (with input 230V ~) the
equipment starts again and repeats the starting cycle;

Indications of error codes by a signalling red light in the release
button;

Programmer times fix for the digital management of signals.
In case of lack of the flame during working the model LMG 25.33
doesn’t stop but repeat the starting cycle
maximum 3 times), if the problem persists, after the fourth starting
the equipment stops .

Comparative table

Conditions for startup

Burner control is reset

All contacts in the line are closed

Fan motor “M” or AGK25 is connected

Air pressure monitor “LP” is in idle position

No undervoltage

Undervoltage

Safety shutdown in the event the mains voltage is lower than typi-
cally AC 160V;

a restart is made when the mains voltage exceeds AC 195V

Reversed polarity protection

If the connections of line (terminal 12) and neutral (terminal 2) have
been exchanged, the burner control will initiatelockout at the end of
"TSA"

Operations key

BV

Fuel valve

FS

Flame presence signal

GP

Gas detection pressure switch

LP

Air pressure switch

LR

Burner's output regulation

M

Fan  motor

R

Safety thermostat or pressure switch

SB

Safety limit

W

Regulation thermostat or pressure switch

Z

Ignition transformer

tw

Waiting time

t1

Pre-ventilation time

TSA

Ignition safety time

t3

Pre-ignition time

t3n

Ignition time during “TSA”

t4

Interval BV-BV2 or BV1-LR

t10

Specified time for air pressure signal

t11

Programmed opening time for actuator SA

t12

Programmed closing time for actuator SA

Startup program

A

Start-up, controlled by LR

-fan command after the waiting time tw for LMG21/25, or after the
period t11 for LMG22.

tw

Waiting time.

During this time the air pressure switch and the flame relay are tested
for correct contact position.

t1

Pre-purgue time.

Purguing of the combustion chamber and the secondary heating sur-
faces with low-load combustion head for LMG21/25, or with fully load
combustion air for LMG22. The affective pre-purgue time comprises
the interval between the end of tw and the start of t3.

TSA Ignition safety time.

Opening of fuel valve BV1; the flame signal must be present at the
terminal 1 up tho the end of TSA.

t3

Pre-ignition time.

Ignition time until the opening of BV1.

t3n

Ignition time during "TSA".

Interval between the start of TSA and the shut-off of ignition transfor-
mer Z. The transformer is shut-off 400ms before the end of TSA.

t4 Interval BV-BV2 or BV1-LR.

Interval between the end of TSA and the consent to the second fuel
valve BV2 or to the load regulator LR.

t10

Specified time for the air pressure signal.

When this time has elapsed, the set value of air pressure must have
built up, else a lock-out is initiated.

t11

Programmed time for the opening of the servocontrol SA,

only with LMG22. The servocontrol SA moves to the low flame posi-
tion.

B-B’ Interval for the flame establishment.

C

Operating position of the burner.

C-D

Burner operation (heat production)

D

Controlled shut-down by LR. 

The burner is shut-off immediately and the flame control device is
ready for a new start.

FUNCTIONS

LMG21.../LMG25...

LMG22...

Old series LGB

New series LMG

---

LMG 25.33

LGB 21.33

LMG 21.33

LGB 22.33

LMG 22.33

Содержание S10

Страница 1: ...Technical Documentation CIB Unigas Campodarsego PD Complying with 90 396 CEE GAS DIRECTIVE MANUAL OF INSTALLATION OPERATION MAINTENANCE GAS BURNERS S10 S18 DOUBLE STAGE VERSION M03952CC Rev 02 04 01...

Страница 2: ...ry equipment only shall be used This unit shall be employed exclusively for the use for which it is meant Any other use shall be considered as improper and therefore dangerous The manufacturer shall n...

Страница 3: ...ls or damage to property for which the manufacturer cannot be held liable Before installation it is recommended that all the fuel supply system pipes be carefully cleaned inside to remove foreign matt...

Страница 4: ...3 OPERATION Available versions AB High low flame 4 BLAST TUBE LENGHT See overall dimensions S Standard L Long 5 DESTINATION COUNTRY see data plate 6 SPECIAL VERSIONS A Standard 7 EQUIPMENT Available...

Страница 5: ...input in kcal h multiply value in kW by 860 Fig 4a Fig 4b A B BL C CL D E F G K J H P M N Q R S10 355 180 275 635 730 340 230 455 108 200 210 125 120 M8 169 7 55 100 S18 355 205 300 660 755 340 230 4...

Страница 6: ...re in combustion chamber Fig 4 Key 1 Boiler 2 Gas pressure port on butterfly valve 3 Sightglass cooling port 4 Water column pressure gauge Curves are referred to a null pressure in combustion head NOT...

Страница 7: ...boilers with a combustion chamber smaller in diameter or shorter than those described in the diagram please contact the supplier to verify that a correct matching is possible with respect of the appl...

Страница 8: ...lves group 3 Leakage control device optional if burner input 1200 kW 4 Bellow joint 5 Manual shut off valve Remove the burner cover Carry out the electrical connections to the multiple con nector as s...

Страница 9: ...e screw VS located under the cover C clockwise increases it anticlockwise decreases it 2 To adjust the flow rate of the air at high flame loosen the nut RA and turn the screw VRA clockwise increases t...

Страница 10: ...rate using the nut RP1 turning it anticlockwise to increase it sign or clockwise to decrease it sig n 3 To adjust the output of the burner in low flame operation use the corresponding servocontrol cam...

Страница 11: ...g 13a Fig 13b Key S Slit indicating the butterfly opening angle DB Stud TG lock nuts TG Butterfly valve opening adjustment stud RA Lock nut VRA Screw for adjusting combustion air to maximum flow rate...

Страница 12: ...y means of the appropriate tool fitted with the servocontrol with SQN30 or by means of a screwdriver affecting on the screw into the cam all other servocontrols Landis SQN30 151 Berger STA6B3 41 Fig 1...

Страница 13: ...t off valve n 5 in Fig 10 until the detected pressure is reduced by 50 Verify CO emissions of the burner if the measured value is less than 80 ppm screw down the adjusting ring nut until the burner lo...

Страница 14: ...LIMINATE THE MALFUNCTION WARNING DURING NORMAL OPERATION THE PARTS OF THE BURNER NEAREST TO THE GENERATOR COUPLING FLANGE CAN BECOME VERY HOT AVOID TOUCHING THEM SO AS NOT TO GET BURNT OPERATION Bring...

Страница 15: ...ctrodes is carried out after removing the combustion head Removing the combustion head Remove the burner from the gas supply line To access the combustion head abd the electrodes slcken the screw VE F...

Страница 16: ...PEATS THE CYCLE NURMER DOESN T SWITCH TO HIGH FLAME BURNER S LOCKUOT DURING OPERATION BURNER STOPS AND REPEATS CYCLE DURING OPERATION BURNER S LOCKOUT AFTER START THE FLAME CONTROL DEVICE REPEATS CYCL...

Страница 17: ...DIS servocontrol for air damper alternate SQN70 224A20 LANDIS servocontrol for air damper alternate ST Group of thermostats or pressure switches STA4 5B0 37 63N21L BERGER servocontrol for air damper S...

Страница 18: ...PART III MAINTENANCE 18 ELECTRICAL DIAGRAMS Electrical diagram 01 320 Rev 3...

Страница 19: ...PART III MAINTENANCE 19 Electrical diagram 01 427...

Страница 20: ...PART III MAINTENANCE 20 SPARE PARTS...

Страница 21: ...80703 2180703 7 CAPACITOR FOR SIMEL MOTOR 6030005 6030005 7 CAPACITOR FOR AEG MOTOR 6030003 6030003 8 TRANSFORMER 2170108 2170108 9 EXTENSION SCREW 2130016 2130027 10 DETECTION CABLE 6050211 6050211 1...

Страница 22: ...GB 21 22 FLAME CONTROLLER 23 LANDIS LMG21 22 25 FLAME CONTROLLER 26 GAS MULTIBLOC REGULATOR DUNGS MB DLE 405 407 410 412 415 420 28 GAS MULTIBLOC REGULATOR DUNGS MB ZRDLE 28 VALVE PROVING SYSTEM DUNGS...

Страница 23: ...n AGK11 s socket Command signal from flame control Input signals Conditions for starting up the burner The burner control must not be locked out The contacts of the gas pressure switch GP the temperat...

Страница 24: ...iance is located a plexiglass lunette under which there is the indicator disc of programme s progress In the event of safety stop the programmer stops The disc shows as follows the position of the pro...

Страница 25: ...stat or pressostat W Safety thermostat or pressostat Z Ignition transformer LGB21 Key programmer s diagram A start up command from regulator R AR main relay B burner operation C program start position...

Страница 26: ...on time t3n Ignition time during TSA t4 Interval BV BV2 or BV1 LR t10 Specified time for air pressure signal t11 Programmed opening time for actuator SA t12 Programmed closing time for actuator SA Sta...

Страница 27: ...lamp switched on Release of the flame control device Press the release button for 0 5 3 seconds Diagnosis of troubles Wait at least 10s Press the release button for 3s Count the number of flashing of...

Страница 28: ...and their combinations MB410 412 Rp 3 4 1 1 4 and their combinations Max operating pressure 360 mbar Output pressure ranges MB S20 S22 4 to 20 mbar MB S50 S52 4 to 50 mbar Media Gases of families 1 2...

Страница 29: ...APPENDIX COMPONENTS CHARACTERISTICS 29...

Страница 30: ...APPENDIX COMPONENTS CHARACTERISTICS 30...

Страница 31: ...APPENDIX COMPONENTS CHARACTERISTICS 31...

Страница 32: ......

Отзывы: