8
by means of the arrow keys, select “Access w-out pass” (access without password - user level), confirm by pressing ENTER.
The other levels require password reserved to the Technical Service, to the Manifacurer, etc.
The menu accessed without password is the following:
Choose “LoadController” and press ENTER: the following menu is shown:
Choose “ControllerParam” and press ENTER: the following menu is displayed:
Choose “
SetPointW1
” and press ENTER:
Curr: it shows the current set-point; use the arrows keys to change it.
NOTE:
the available range depends on the probe used; the measure unit of the detected data and its relevant limits are set by “Service”
level parameters.
Once the new set-point is set, confirm by pressing ENTER, otherwise exit without changings by pressing ESC.
Press ESC to exit the set-point programming mode.
Once the temperature set-point W1 is imposed, set the Switch-on (SDon) and the Switch-off (SDoff) point of the 2-position controller:
To set these values, select the item SD_ModOn (SDOn), by scrolling down the “Load controller” menu with the arrow keys and press
ENTER:
Access w-out PW
Access Serv
Access OEM
Access LS
BurnerControl
RatioControl
O2Contr./Guard.
LoadController
ControllerParam
Configuration
Adaption
SW Version
ContrlParamList
MinActuatorStep
SW_FilterTmeCon
SetPointW1
SetpointW1
Curr: 90°
New: 90°
S
etpoint
Act
ua
l v
a
l
u
e
S
Doff
W
S
Don
Содержание RX1025.1
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 45: ...User manual Siemens LMV 5x M12914CA Rev 0 03 2008...
Страница 46: ......
Страница 57: ......
Страница 58: ......
Страница 59: ......
Страница 62: ...Annex1 Example for motor cable...
Страница 63: ......
Страница 64: ...Annex 2 Example for sensor cable...
Страница 65: ......
Страница 66: ......
Страница 70: ......