18
Pressure adjusting range
The pressure adjusting range, upstream the gas valves group, changes according to the spring provided with the valve group.
Keys
Siemens VGD valves with SKP actuator
Once the train is installed, connect electrically all its elements: gas valves group, pressure
switches, gas proving system.
ADJUSTMENTS
Siemens SKP actuator
ATTENTION:
once the gas train is mounted according to the diagram on Fig. 11, the gas proving test mus be perfor-
med, according to the procedure set by the laws in force.
ATTENTION:
before starting the burner up, be sure that the manual cutoff valves are open and check that the pres-
sure upstream the gas train complies the value quoted on paragraph “Technical specifications”. Be sure that the
mains switch is closed.
.
ATTENTION:
During commissioning operations, do not let the burner operate with insufficient air flow (danger of formation
of carbon monoxide); if this should happen, make the gas decrease slowly until the normal combustion values are achieved.
WARNING: NEVER LOOSE THE SEALED SCREWS! OTHERWISE, THE DEVICE WARRANTY WILL BE IMMEDIA-
TELY INVALIDATE!
IMPORTANT! the combustion air excess must be adjusted according to the in the following chart:
Recommended combustion parameters
Fuel
Recommended (%) CO
2
Recommended (%) O
2
Natural gas
9 ÷ 10
3 ÷ 4.8
2
1
1 spring
2 cap
:
Performance range (mbar)
0 - 22
15 - 120
100 - 250
Spring colour
neutral
yellow
red