
C.I.B. UNIGAS
- M039241CB
12
Tab. 1 - Supply pipeline hydraulic scheme 3ID0024, pump n.4
Burner adjustments
The table below shows indicative values of temperature and pressure to be set on the burner devices, according to the viscosity of the
heavy oil used. The oil temperature should be set on TR resistor thermostat in order to get about 10 - 40 cSt (2 - 5 °E) viscosity at the
nozzle. The oil temperature must no exceed 160°C.
Tab. 2 - Burner - hydraulic scheme 32ID-01, pump n.2
HEAVY OIL VISCOSITY AT 50 °C
PIPELINE
PRESSURE
PIPELINE
TEMPERATURE
cSt (°E)
bar
°C
< 50 (7)
1- 2
20
> 50 (7)
< 110 (15)
1- 2
50
> 110 (15)
< 400 (50)
1- 2
65
> 400 (50)
< 4000 (530)
1- 2
100
VISCOSITY
AT 50 °C
OIL PRESSURE
AFTER
BURNER PUMP
(N. 2 in 3I2D-01)
OIL PRESSURE
AFTER OIL
METERING VALVE
(N. 14 IN 3I2D-01)
TEMPERATURE OF
THE PRE-HEATING
RESISTORS
THERMOSTAT TR
TEMPERATURE OF
THE RESISTORS
SAFETY
THERMOSTAT TRS
TEMPERATURE OF
THE PLANT
ENABLING
THERMOSTAT TCI
min
max
min
max
min
max
°E
bar
bar
°C
°C
°C
< 50 (7)
5
8
0.5
2
70
95
190
50
> 50 (7)
< 110 (15)
5
8
0.5
2
75
105
190
60
> 110 (15) < 400 (50)
5
8
0.5
2
100
140
190
70
> 400 (50) <4000 (530)
5
8
0.5
2
140
160
190
70
ATTENTION: Atomizing air pressure is tipically set at 0.1 ÷ 0.3 bar lower than oil pressure.
ATTENTION: on High flame, set atomising air pressure at 1.8 ÷ 2 bar.
Содержание PBY70
Страница 7: ...C I B UNIGAS M039241CB 7 Overall dimensions mm boiler recommended drilling template ...
Страница 16: ...C I B UNIGAS M039241CB 16 HYDRAULIC DIAGRAMS Fig 8 Hydraulic diagram 3ID0024 ...
Страница 18: ...C I B UNIGAS M039241CB 18 Fig 9 Hydraulic diagram 3I2D 01 ...
Страница 23: ...C I B UNIGAS M039241CB 23 Hydraulic connections Key G Gas A Air O Oil CA Cleaning air Fig 12 G G O A CA A O CA ...
Страница 37: ...C I B UNIGAS M039241CB 37 ...
Страница 42: ......
Страница 43: ......