PART III: OPERATION
32
Choose the type of fuel by turning the switch, on the burner control panel.
CAUTION:
if the fuel chosen is light oil, be sure the cutoff valves on the feed and return pipes are open.
Check the control box is not locked; if so, reset it by means of the reset LMV button.
Check the series of thermostats and pressure switches allow the burner to start.
Gas operation
Choose the type of fuel by turning the switch, on the burner control panel.
Check that the control box is not in the lockout position (light
B
on); in case unlock it by pressing the relevant key (for further infor-
mation on the LMV5.., see the related manual).
Check that the pressure switches/thermostats series enables the burner operation.
Check that the gas pressure is sufficient (signalled by an error code on the AZL2.. display).
At the beginning of the start-up cycle, the actuator drives the air damper to the maximum opening position, then the fan motor
starts up: the pre-purge phase begins. During the pre-purge phase, the air damper complete opening is signalled by the light
F
on
(see front panel).
At the end of the pre-purge, the air damper is driven to the ignition position, the ignition transformer is energised (signalled by the
light
H
on the front panel) then, few seconds later, the EV1 and EV2 gas valves are energised (light L and I on the front panel).
Few seconds after the gas valves opening, the ignition transformer is de-energised and light
H
turns to off.
The burner operates in the low flame stage; few seconds later the two-stages operation begins and the burner output increases or
decreases, driven by the external thermostats (progressive burners) or by the modulator (fully-modulating burners).
.
Light oil operation
The fan motor starts and the pre-purge phase as well. Since the pre-purge phase must be carried out at the maximum air rate, the
control box drives the actuator opening and when the maximum opening position is reached, the pre-purge time counting starts.
At the end of the pre-purge time, the actuator is in the light oil ignition position: the ignition transformer is energised (lamp
L
on); the
ignitor gas valves and the light oil valves open. Few seconds after the valves opening, the transformer is de-energised and lamp
L
turns off.
The burner is now operating, meanwhile the actuator goes to the high flame position; after some seconds, the two-stage operation
begins; the burner is driven automatically to high flame or low flame, according to the plant requirements.Operation in high or low
flame is signalled by LED
N
on the burner control panel.