
PART I: SPECIFICATIONS
13
POWER REDUCTION WITH REFERENCE TO THE BURNER OPERATING CURVE
Since depowering the burner operating range is equivalent to increasing the burner power by the same percentage, the quickest proce-
dure is described point by point below:
Choosing the burner without taking flue gas recirculation into account
estimate the amount of recirculation (see figure below) required to ensure a certain NOx value as a function of the heat load of the
boiler, for that burner
multiply the required burned power by the depowering factor expressed as follows
multiply the back pressure in the combustion chamber by the depressurisation factor squared (pressure losses vary with the
square of the change in flow rate)
choose the burner considering the new power and back pressure value
if the burner size is insufficient, a larger machine must be selected, the depowering factor must be re-checked and the above pro-
cedure repeated.
Burne
r
po
wer reductio
n %
N880X
-FGR
Thermic Load (MW/m
3
)
Burner pow
er
re
duction %
N925X
-FGR
Thermic Load (MW/m
3
)
Содержание N880X-FGR
Страница 14: ...PART I SPECIFICATIONS 14 Burner power reduction N1060X FGR Thermic Load MW m3 ...
Страница 59: ......