9
Low NOx burners Technical specifications
* NOTE ON THE WORKING SERVICE: the control box automatically stops after 24h of continuous working. The control box
immediately starts up, automatically.
BURNER TYPE
NGX280
M-.xx...x.25
NGX280
M-.xx...x.32
NGX280
M-.xx...x.40
Output
min.- max. kW
60 - 190
Fuel
Natural gas
Category
(see next paragraph)
Gas rate
min.- max. (Stm
3
/h)
6,4 - 20
Gas pressure
min.- max. mbar
(Note2)
Power supply
230V - 50Hz
Total power consumption
kW
0,55
Electric motor
kW
0,25
Protection
IP40
Valves size
/
Gas connection
1” / Rp1
1”
1/4
/ Rp 1
1/4
1”
1/2
/ Rp 1
1/2
Operation
Progressive - Fully modulating
NOx emissions
Class 3 - EN676/2008
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service *
Intermitent
BURNER TYPE
NGX350
M-.xx...x.25
NGX350
M-.xx...x.32
NGX350
M-.xx...x.40
Output
min.- max. kW
65 - 260
Fuel
Natural gas
Category
(see next paragraph)
Gas rate
min.- max. min.-
max.(Stm
3
/h)
7 - 27.5
Gas pressure
min.- max. mbar
(Note2)
Power supply
230V - 50Hz
Total power consumption
kW
0,67
Electric motor
kW
0,37
Protection
IP40
Valves size
/
Gas connection
1” / Rp1
1”
1/4
/ Rp 1
1/4
1”
1/2
/ Rp 1
1/2
Operation
Progressive - Fully modulating
NOx emissions
Class 3 - EN676/2008
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service *
Intermitent
Note1:
All gas flow rates are referred to Stm
3
/h (1013 mbar absolute pressure, 15 °C temperature) and are valid for G20 gas (net
calorific value H
i
= 34.02 MJ/Stm
3
); for L.P.G. (net calorific value H
i
= 93.5 MJ/Stm
3
)
Note2:
Maximum gas pressure = 360mbar (with
Dungs MBDLE/MBC valves)