36
SETTING GAS AND AIR FLOW RATE
To perform the adjustments, unscrew the fixing screws and remove the burner’s cover (see Fig. 42-2)
Startup Output
The start-up heat output shall not exceed 120 kW (single stage burners) or 1/3 of nominal output (double-stage, progressive or fully
modulating burners). In order to comply with these requirements, burners are provided with butterfly valve and/or slow-opening safety
valve. On double-stage, progressive or modulating burners, the low flame ouptut must be higher than the minimum ouptut quoted in the
performance curve (page 11).
Adjustments - brief description
Check that the combustion parameters are in the suggested limits.
Check the flow rate measuring it on the counter or, if it was not possible, verifying the combustion head pressure by means of a dif-
ferential pressure gauge, as described on par. “Measuring the gas pressure in the combustion head” on page 15.
Then, adjust the combustion by settin the “air/gas ratio” curvepoints (see the LMV2x attached manual).
Set, now, the low flame output, in order to avoid the low flame output increasing too much or that the flues temperature gets too low
to cause condensation in the chimney.
ATTENTION:
before starting the burner up, be sure that the manual cutoff valves are open and check that the pres-
sure upstream the gas train complies the value quoted on paragraph “Technical specifications”. Be sure that the
mains switch is closed.
.
ATTENTION:
During commissioning operations, do not let the burner operate with insufficient air flow (danger of formation
of carbon monoxide); if this should happen, make the gas decrease slowly until the normal combustion values are achieved.
WARNING: NEVER LOOSE THE SEALED SCREWS! OTHERWISE, THE DEVICE WARRANTY WILL BE IMMEDIA-
TELY INVALIDATE!
Fig. 42
Keys
1
Valve group
2
Cover
3
Control panel
4
Blast tube
IMPORTANT! the combustion air excess must be adjusted according to the in the following chart:
Recommended combustion parameters
Fuel
Recommended (%) CO
2
Recommended (%) O
2
Natural gas
9 ÷ 10
3 ÷ 4.8
LPG
11 ÷ 12
2.8 ÷ 4.3
3
1
4
2