C.I.B. UNIGAS - M039219CA
15
Assembling the gas grain
To assemble the gas train, proceed as follows:
Fig. 4 - Example of gas train
To mount the gas train, proceed as follows:
1-a) in case of threaded joints: use proper seals according to the gas used;
1-b) in case of flanged joints: place a gasket (no. 1A..1E - Fig. 4) between the elements
NOTE:
the bellow joint, the manual cock and the gaskets are not part of the standard supply.
The procedures of installation fo the gas valves are showed in the next paragraphs, according to the gas train used:
z
threaded gas trains with Multibloc Dungs MBC..SE 1200 or Siemens VGD20..
z
flanged gas trains with Multibloc Dungs MBC..SE 1900-3100-5000 or Siemens VGD40..
Siemens VGD20.. and VGD40.. gas valves - with SKP2.. (pressure governor)
Mounting
z
When mounting the VGD.. double gas valve, two flanges are required (as for VGD20.. model, the flanges are threaded);
z
to prevent cuttings from falling inside the valve, first fit the flanges to the piping and then clean the associated parts;
z
install the valve;
z
the direction of gas flow must be in accordance with the direction of the arrow on the valve body;
z
ensure that the bolts on the flanges are properly tightened;
z
ensure that the connections with all components are tight;
z
make certain that the O-rings and gaskets between the flanges and the double gas valve are fitted.
z
Connect the reference gas pipe (
TP
in figure), to the gas pressure nipples placed on the gas pipe, downstream the gas valves: gas pres-
sure must be measured at a distance that must be at least 5 times the pipe size .
Leave the blowhole free (
SA
in figure). Should the spring fitted not permit satisfactory regulation, ask one of our service centres for a
suitable replacement.
ATTENTION:
once the gas train is mounted according to the diagram on Fig. 4, the gas proving test mus be performed,
according to the procedure set by the laws in force.
1A
5
1B
4
1C
2
1D
1E
3
Keys
1A..1E
Gasket
2
Gas filter
3
Gas valves group
4
Bellow joint
5
Manual cock
”direction” arrows for installation
gas supply network
Содержание HTP90A
Страница 47: ...C I B UNIGAS M039219CA 47 Wiring diagram 21 002 3...
Страница 48: ...C I B UNIGAS M039219CA 48...
Страница 49: ...C I B UNIGAS M039219CA 49...
Страница 50: ...C I B UNIGAS M039219CA 50 WIRING DIAGRAM Cod 11 336 2...
Страница 51: ...C I B UNIGAS M039219CA 51...
Страница 52: ...C I B UNIGAS M039219CA 52...
Страница 53: ...C I B UNIGAS M039219CA 53 WIRING DIAGRAM Cod 11 339 2...
Страница 54: ...C I B UNIGAS M039219CA 54...
Страница 55: ...C I B UNIGAS M039219CA 55...
Страница 56: ...C I B UNIGAS M039219CA 56...