PART I: SPECIFICATIONS
7
Technical Specifications
Gas categories and countries of application
BURNER TYPE
C85A M-..
C120A M-..
C85A L-..
C120A L-..
Output
min. - max. kW
230 - 850
300 - 1200
230 - 850
300 - 1200
Fuel
Natural gas
L.P.G.
Category
see next paragraph
I
3B/P
Gas flow rate
min.-max. Stm
3
/h
24 - 90
32 - 127
8.6 - 32
11,2 - 45
Gas pressure
min.-max. mbar
(see Note 2)
Electric supply
230V 3~ / 400V 3N ~ 50Hz
Total power consumption
kW
1,6
2
1,6
2
Fan motor
kW
1,1
1,5
1,1
1,5
Protection
IP40
Operation
Progressive - Fully modulating
Valves size / Gas connection - 32
1"
1/4
/
Rp 1
1/4
-
1"
1/4
/
Rp 1
1/4
-
Valves size / Gas connection - 40
1"
1/2
/
Rp 1
1/2
1"
1/2
/
Rp 1
1/2
1"
1/2
/
Rp 1
1/2
1"
1/2
/
Rp 1
1/2
Valves size / Gas connection - 50
2"
/
Rp 2
2"
/
Rp 2
2"
/
Rp 2
2"
/
Rp 2
Valves size / Gas connection - 65
2"
1/2
/
DN65
2"
1/2
/
DN65
2"
1/2
/
DN65
2"
1/2
/
DN65
Valves size / Gas connection - 80
-
3"
/
DN80
-
3"
/
DN80
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service*
Continuous
Note1:
All gas flow rates are referred to Stm
3
/ h (1.013 mbar absolute pressure, 15 °C temperature) and are valid for G20 gas
(net calorific value H
i
= 34,02 MJ / Stm
3
); for L.P.G. (net calorific value H
i
= 93,5 MJ / Stm
3
)
Note2:
Maximum gas pressure = 360 mbar (with
Dungs MBDLE)
= 500 mbar (with
Siemens VGD or Dungs MultiBloc MBE)
Minimum gas pressure = see gas curves.
Note3:
Burners are suitable only for indoor operation with a maximum relative humidity of 80 %
GAS CATEGORY
COUNTRY
I
2H
AT, ES, GR, SE, FI, IE, HU, IS, NO, CZ, DK, GB, IT, PT, CY, EE, LV, SI, MT, SK, BG, LT, RO, TR, CH
I
2E
LU, PL
I
2E( R ) B
BE
I
2EK
NL
I
2ELL
DE
I
2Er
FR
Содержание C120A
Страница 46: ......
Страница 47: ......
Страница 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Страница 56: ...8...
Страница 57: ...9 1 4 1 Servomotor wiring example 1 4 2 Bus cable wiring on LMV5x and AZL doors 1 4 3 EARTH connection example...
Страница 60: ...12 2 2 LMV5x program structure...
Страница 87: ...39...
Страница 94: ......
Страница 95: ......
Страница 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Страница 98: ...Annex1 Example for motor cable...
Страница 99: ......
Страница 100: ...Annex 2 Example for sensor cable...
Страница 101: ......
Страница 102: ......
Страница 106: ......