PART I: SPECIFICATIONS
11
Checking the proper gas train size
Pressure in the Network / gas flow rate curves
Natural Gas burners
To check the proper gas train size, it is necessary to the available
gas pressure value upstream the burner’s gas valve. Then subtract
the backpressure. The result is called
pgas.
Draw a vertical line
matching the furnace input value (600kW, in the example), quoted
on the x-axis, as far as intercepitng the network pressure curve,
according to the installed gas train (DN65, in the example). From the
interception point, draw an horizontal line as far as matching, on the
y-axis, the value of pressure necessary to get the requested furnace
input. This value must be lower or equal to the
pgas
value, calcula-
ted before.
GAS PRESSURE
IN
THE NETW
ORK
m
b
ar
C85A M-..
Stm
3
/h
C120A M-..
Stm
3
/h
GAS PRESSURE IN THE NETWORK
mbar
C120A L-..
Stm
3
/h
ATTENTION: the gas rate value is quoted on the x-axis, the related network pressure is quoted on the y-axis
(pressure value in the combustion chamber is not included). To know the minimum pressure at the gas train inlet,
necessary to get the requested gas rate, add the pressure value in the combustion chamber to the value read on
the y-axis.
The values in the diagrams refer to
natural gas
with a calorific value of 8125 kcal/Stm
3
(15°C, 1013 mbar) and a density of
0.714 kg/Stm
3
.
0
5
10
15
20
25
100
200
300
400
500
600
700
800
900
Potenza / Output (kW)
Minima pressione gas in
rete / Minimum inlet gas
pressure (mbar)
Rp 2" (50)
DN65
Power kW
mini
mum g
a
s pr
ess
ure
in
the
ne
twor
k
mba
r
DN65
Содержание C120A
Страница 46: ......
Страница 47: ......
Страница 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Страница 56: ...8...
Страница 57: ...9 1 4 1 Servomotor wiring example 1 4 2 Bus cable wiring on LMV5x and AZL doors 1 4 3 EARTH connection example...
Страница 60: ...12 2 2 LMV5x program structure...
Страница 87: ...39...
Страница 94: ......
Страница 95: ......
Страница 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Страница 98: ...Annex1 Example for motor cable...
Страница 99: ......
Страница 100: ...Annex 2 Example for sensor cable...
Страница 101: ......
Страница 102: ......
Страница 106: ......