0014_Installation_Operation_Manual
Draft
Page 14 of 22
Copyright 2017 Unifire
7.1
Fuses
Fuses are provided on connections X808, X809, X810, X811 and X800. Fuses are located on the
underside of the field IO board.
Connection
Fuse
Rating
X808
F802
2.5A 300V
X809
F803
2.5A 300V
X810
F804
2.5A 300V
X811
F805
2.5A 300V
X800
F801
10A 300V
Integrity of fuses can be checked with a multi-meter without removing the boards from the enclosure.
Figure 5 - Fuse Test Points
To replace fuses it is recommended that the electronics assembly is removed from the enclosure in the
manner described in the preceding section.
Once removed, release the field IO board from the main board by removing the 4 screws and PCB
standoffs located in the corners of the board. Carefully rotate the field IO board forwards to access the
fuses. Replace with radial board mount fuses of equivalent rating. Reinstall the electronics assembly
before powering up.