Touch Screen
34
4.15
PASSWORD AND PROTECTIONS
There are more protection and password levels.
An initial distinction includes the following three access levels:
-
User’s level
-
Service level
-
Manufacturer’s level
To each of these three different levels you can access from the “Configuration” screen, previously inserting a dedicated password.
The user’s password, default set to “0”, can be modified by accessing to user’s parameters (see Paragraph 3.6.5.1).
The service’s password can be modified by accessing to service parameters (see Paragraph 3.6.5.2).
The manufacturer’s password can be modified by accessing to manufacturer’s parameters (see Paragraph 3.6.5.3).
Once the password has been inserted, is allowed the full navigation in all the pages in which the access has been granted.
Once the navigation has terminated, log-out should be done by a touch on the related symbol which is flashing in the low-right side
of the home page.
The log-out happens automatically after 5 minutes of touch-screen inactivity or after 20 minutes from the access to the current level
of protection. These timing values can be modified from service or manufacturer’s parameter.
There is a password to unlock the screensaver, set by default to “0” and modifiable by accessing to user’s parameters (see
Paragraph 3.6.5.1).
5
REMOTE ACCESS
The device can interact with the local network by an Ethernet port access.
The access must be enabled through a manual installation in the local network (no DHCP services are forecasted).
The device can communicate through browsers compatible with HTML 4.01 and/or TPFT services RFC 1350 compliant.
The web-server interface is a textual type and is below described.
5.1
SECURITY
The insertion of the touch screen in a LAN network must guarantee a higher level security, which must be ensured by the installer,
against undesired attacks from outside agents (hacker).
The device will not enforce security systems and will assume that anyone who interacts from the network is enabled to do so.
5.2
LOCAL WEB SERVER
A local web-server has been implemented to access to Touch Screen from the local network with a browser HTML 4.01 compatible.
To access check on page “
Ethernet Configuration
” accessible from the home page by pushing on the following icon:
Accessing by service/manufacturer’s allowances, it is possible to modify the default values of each address. After having modified
the addresses, please shut down and restart the Touch Screen in order to validate the modifications.
After carrying out the connection, you can display the following pages:
Содержание TOUCH SCREEN N
Страница 1: ...USER S AND INSTALLER S MANUAL LCD Touch Screen Centralized Remote Controller TOUCH SCREEN_N...
Страница 42: ......
Страница 43: ......