OPERATING LIMITS 

19.1

 

EVAPORATOR WATER FLOW RATE 

The nominal water flow rate is referred to a ∆T equ

al to 5°C, between the evaporator’s inlet and outlet temperatures. The allowed 

maximum flow rate is corresponding to ∆T=3°C. Higher values may produce too high pressure drops. The allowed minimum water 

flow rate is corresponding to ∆T=8°C. Insufficient val

ues of water flow may produce too low evaporating temperatures according 

to the operating status with the intervention of safety devices which would stop the unit and, in some particular cases, the water 

can freeze in the evaporator coil which can breakdown the refrigeration circuit  or causes the  increasing  of the condensing 

pressure with the shutdown risk of the appliance and the compressor could be damaged. 

We enclosed below a most accurate table showing the minimum water flow that should be ensured for the plate heat exchanger 

in order to have the proper operation of unit as a function of the model (

note:

 the water flow switch is used for preventing the 

freezing sensor from failure in the case of insufficient water flow but it does not ensure the minimum flow rate required in order 

the unit can work properly) 

Models 

HP_OWER 

250N 

350N 

500N 

Cooling capacity for reference [kW] 

21,02 

26,90 

36,21 

Minimum water flow rate that to ensure [L/s] 

0,63 

0,80 

1,08 

As a first approach, and in the absence of other detection systems, the proper flow rate for getting the best performance from 

your unit can be found at maximum speed of the circulator, using the pressure gauges for controlling the pressure difference 

between the return and the delivery water on the outside water connections of the unit and make sure that such value is equal or 

less than the static pressure indicated on the curves shown in paragraph 15 for the respective models and if it’s necessary change 

the settings (for the related circulator) that are reported in the control manual. 

19.2

 

COLD WATER TEMPERATURE (SUMMER OPERATION) 

The minimum temperature that is allowed at the evaporator’s outlet is 5°C:  for lowest temperatures  the unit should undergo 

some necessaries structural modifications and different setting parameters of the controller with micro-processor.  In this case 

please  contact our company for the feasibility study and evaluation of changes to be made according to your requests. The 

maximum temperature that can be maintained at the outlet of the evaporator is 25°C. Higher temperatures (up to a maximum of 

40°C) can anyway be tolerated during transitions and start-up phases of the system. 

19.3

 

HOT WATER TEMPERATURE (WINTER OPERATION) 

Once the system is working at the right temperature, the inlet hot water temperature should not be lower than 25°C; the lowest 

values that are not related to transitional or start-up stages may cause system’s malfunction and possible compressor 

breakdowns. The maximum outlet water temperature should not exceed 60°C. At this temperature, the power consumption and 

performance in terms of C.O.P. are enhanced if the outdoor temperature is higher than 5°C, even if the unit is still able to work up 

to the limit of -15°C (-25°C for versions with injection). 

For higher temperatures than those pointed out, especially if have a concomitant with the reduction of the water flow rate, it may 

cause abnormalities to the normal operating of the unit, or the safety devices act in critical cases. 
The maximum power consumption of the heat pump alone will take place during the operation with outlet water temperature of 

60°C and outdoor temperature of -15°C(-25°C for versions with injection) 

19.4

 

AMBIENT AIR TEMPERATURE 

The units are designed and manufactured to operate, in summer operation, with the condensate control, with outdoor air 

temperatures ranging between -10°C and 46°C. While operating as a heat pump, the allowed range of the outdoor temperature 

goes from -15°C (-25°C for versions with injection) to 40°C as a function of the water outlet temperature as indicated in the below 

table. 

     Operation limits 

Water chiller mode 

Ambient temperature 

Min.-10°C               Max. +46°C 

Water outlet temperature 

Min. +5°C               Max. +25°C 

Heat pump mode

 

Ambient temperature (standard/injection version) 

Min. -15/-25°C      Max. +30°C 

Water outlet temperature (standard/injection version) 

Min. +25°C  Max. +60°C/+65°C 

Heat pump mode for sanitary hot water

 

Ambient temperature with maximum water temperature 48°C (standard/injection version)  Min. -15 / -25°C    Max. +40°C 

Ambient temperature with maximum water temperature 55°C (standard/injection version)  Min. -15 / -25°C    Max. +35°C 

Water outlet temperature (standard/injection version) 

Min. +20°C  Max. +60°C/+65°C 

(*) With additional electric heater (not supplied) 

Below the operation limits are reported, in the case of air conditioning and sanitary hot water production. 

Содержание HP_OWER 250N

Страница 1: ...User s and Installer s Manual 250 350 500 N...

Страница 2: ...optional module terminal block CODE 00264034 13 7 START UP 14 7 1 POWER ON OF THE UNIT 14 8 INDICATIONS FOR THE USER 14 9 SHUTDOWNS FOR LONG PERIODS 14 10 MAINTENANCE AND PERIODICAL CONTROLS 15 10 1...

Страница 3: ...unit it refers to It has to be stored in a safe place away from the dust and moisture It has to be accessible to all users who shall consult it any time they are in doubt on how to operate the equipm...

Страница 4: ...well as any applicable local laws and authorized specifications The execution of all works must be performed by skilled and qualified personnel competent in the existing rules in different countries T...

Страница 5: ...ce s health and safety including 89 391 CEE 89 686 CEE 89 655 CEE 2009 104 CE 86 188 CEE and 77 576 CEE directives Every employer shall implement such norms and ensure that workers to respect them It...

Страница 6: ...TWA 1000 ml m for each of the two components Respiratory protection For rescue and maintenance operation in storage tanks use self contained respirator The vapors are heavier than air and can cause su...

Страница 7: ...ng the unit immediately check its integrity The unit left the factory in perfect condition any eventual damage has to be questioned to the carrier and recorded on the Delivery Note before signing it T...

Страница 8: ...rubber band between basement and unit base frame It is also possible to install anti vibration supports springs or rubbers to keep vibrations at a very low level An absolute care has to be taken to en...

Страница 9: ...ing water for the plant please refer to UNI 8065 CAUTION The INVERTER control system is able to manage minimum water contents in the plant up to a value of 75 liters for the model HP_OWER 250 of 105 l...

Страница 10: ...R 4WV CYCLE REVERSING VALVE LR LIQUID RECEIVER EEV ELECTRONIC EXPANSION VALVE FL FILTER M AXIAL FAN SE OUTDOOR AIR TEMPERATURE SENSOR P CIRCULATOR ON BOARD UNIT IN WATER INLET TEMPERATURE OUT WATER OU...

Страница 11: ...must be installed in TN S TT power supply grounding systems The electrical installation must be carried out in accordance with norms in force WARNING The supply voltage s fluctuations cannot exceed 5...

Страница 12: ...utral conductor N 6 6 2 User s terminal block L1F1 L1F1 L2F1 L2F1 L3F1 L3F1 N 1 N 2 N 1 N 2 PE 1 PE 1 L3 1 L3 2 L3 1 L3 2 HPS HPS 12AC1 12N1 12AC1 12N1 DO1 DO3 DO5 DO4 DO6 DO7 DO2 DO7N DO6N DO5N DO4N...

Страница 13: ...the unit s front panel For the configuration of the functionalities please check the control manual supplied with the unit DO1E DO3E DO5E DO4E ST5E ST6E DO2E DO1EN DO1EN DO1E DO3E DO5E DO4E ST5E ST6E...

Страница 14: ...hanges of this seasonal operating mode have to be avoided in order to prevent severe damages to compressors WARNING When you first install and start up the unit make sure that the unit is working prop...

Страница 15: ...entering the inner components of the unit be sure that the power supply is disconnected The compressor s heads and discharge pipes are usually at high temperature levels Be very careful when operating...

Страница 16: ...rolled substances and for this reason it has to be subjected to the mentioned norms A particular care is recommended during service operations in order to reduce as much as possible any refrigerant lo...

Страница 17: ...0 27 04 29 1 36 21 38 4 36 36 38 3 Power input 2 kW 6 48 6 35 9 1 8 96 12 49 12 45 EER 2 W W 3 24 3 33 2 96 3 02 2 90 2 92 SEER 5 W W 3 98 4 00 4 03 Heating Heating capacity 3 kW 24 72 27 2 24 57 27 2...

Страница 18: ...70 dB A 74 dB A 77 dB A Precautions for installation and maintenance Read precautions for installation and maintenance at specific chapters on user s and installation s manual PRODUCT FICHE HP_OWER f...

Страница 19: ...5 94 Tj bivalent temperature Pdh 16 4 kW Tj bivalent temperature COPd 2 36 Tj operation limit temperature Pdh 13 8 kW Tj operation limit temperature COPd 1 76 For air to water heat pumps Tj 15 C if T...

Страница 20: ...89 Tj bivalent temperature Pdh 20 5 kW Tj bivalent temperature COPd 2 12 Tj operation limit temperature Pdh 17 7 kW Tj operation limit temperature COPd 1 83 For air to water heat pumps Tj 15 C if TOL...

Страница 21: ...5 76 Tj bivalent temperature Pdh 31 4 kW Tj bivalent temperature COPd 2 23 Tj operation limit temperature Pdh 26 6 kW Tj operation limit temperature COPd 1 73 For air to water heat pumps Tj 15 C if TO...

Страница 22: ...W Tj 12 C COPd 3 68 Tj bivalent temperature Pdh 11 6 kW Tj bivalent temperature COPd 1 78 Tj operation limit temperature Pdh 9 8 kW Tj operation limit temperature COPd 1 56 For air to water heat pumps...

Страница 23: ...W Tj 12 C COPd 3 88 Tj bivalent temperature Pdh 20 7 kW Tj bivalent temperature COPd 1 59 Tj operation limit temperature Pdh 17 6 kW Tj operation limit temperature COPd 1 33 For air to water heat pump...

Страница 24: ...W Tj 12 C COPd 3 51 Tj bivalent temperature Pdh 23 0 kW Tj bivalent temperature COPd 1 78 Tj operation limit temperature Pdh 19 6 kW Tj operation limit temperature COPd 1 56 For air to water heat pump...

Страница 25: ...with the UNI EN ISO 9614 2 13 ELECTRIC DATA OF THE UNIT AND AUXILIARIES Power supply of the unit V Hz 400 3 50 Remote control circuit V Hz 12 1 50 Control board circuit V Hz 12 1 50 Fans power supply...

Страница 26: ...ve circulator with the possibility of choice between constant P and variable P 15 2 MODEL HP_OWER 500N Configuration with integrated circulator control via 0 10 volt analogic signal Configuration with...

Страница 27: ...SS CURVES OF THE HYDRONIC CIRCUIT We obtain the pressure head of the circulating pump from the addition of the head losses of the hydronic circuit and the available head pressure For example for the m...

Страница 28: ...rmal insulation which reduces at very low outside temperatures the heat losses of 2 compared to a standard insulation 18 2 SSL Cod 00264038 The super silenced unit with SLN accessory is provided not o...

Страница 29: ...lity study and evaluation of changes to be made according to your requests The maximum temperature that can be maintained at the outlet of the evaporator is 25 C Higher temperatures up to a maximum of...

Страница 30: ...ssure drops correction factor The water flow rate and pressure drop correction factors are to be applied directly to the values given for operation without glycol The water flow rate correction factor...

Страница 31: ...Max Packing height mm Max Packing height with AXITOP Versions SSL mm HP_OWER 250N 350N 1673 1906 1785 2030 HP_OWER 500N 1745 1910 1890 2055 Some units could be shipped with another type of packaging...

Страница 32: ...he units is indicative and useful to present the main components and can therefore vary from the purchased one The front panel is closed The front panel is open at 180 Disconnecting switch with door l...

Страница 33: ...n models there are also other components installed in an additional plate at the bottom left side of the electric box On board terminal block and user s terminal block Support boards Transformer Drive...

Страница 34: ......

Страница 35: ......

Страница 36: ...s It also reserves the right to modify its products as deemed necessary or useful without jeopardising their essential features 46033 casteldario mantova italia tel 39 0376 57001 fax 39 0376 660556 in...

Отзывы: