5.4
HYDRAULIC CONNECTIONS
The hydraulic connections have to be installed in accordance with national and local regulations; pipes can be made up of steel,
galvanized steel or PVC. Pipes have to be designed depending on the nominal water flow and on the hydraulic pressure drops of
the system. All pipes have to be insulated with closed-cell material of adequate thickness. Chillers have to be connected to piping
by means of flexible joints. Piping should include:
•
Hole thermometers to monitor the system’s temperature.
•
Manual gate valves to separate the chiller from the hydraulic circuit.
•
Y-shaped metallic filter (to be mounted on the inlet pipe) with a mesh not larger than 1mm.
•
Charging group and discharge valve, where necessary.
WARNING: Make sure that, when designing the pipe length and diameter, do not exceed the maximum head loss
on the plant side, please see the technical data given in the table of Paragraph 12 (available pressure head).
WARNING: Connect the pipes to the attacks by using always key against key system.
WARNING: The expansion vessel have a limited volume. The installator have to provide a further expansion vessel
if it is necessary.
WARNING: Unit water inlet pipe have to be in correspondence with the connection labelled: ”WATER INLET”,
otherwise the evaporator may freeze.
WARNING: It is compulsory to install on the WATER INLET connection a metallic filter with a mesh not larger than
1mm. Should the water flow switch be altered or should the filter not be installed, the warranty will no longer be
valid. The filter have to be kept clean, so make sure it is clean after the unit has been installed, and then check it
periodically.
All units are standard supplied with the water flow switch (factory installed). Should the water flow switch be
altered, removed, or should the water filter not be installed on the unit, the warranty will be invalidated. Please
refer to the wiring diagram for the water flow switch electric connections.
1. Vibration-damping joint
2. Gate valve
3. Filling / Drain valve
4. Differential by-pass
5. Filtre
6. System expansion vessel
Heating / Cooling system
Содержание HP OWER 120
Страница 1: ...User s and Installer s Manual 60 90 120 150 ...
Страница 3: ...HP_OWER 3 ...
Страница 26: ...HP OWER 26 13 WATER PUMP CURVES 13 1 MODELS HP_OWER 60 90 13 2 MODELS HP_OWER 120 150 ...
Страница 29: ...HP_OWER 29 16 DIMENSIONS 16 1 MODELS HP_OWER 60 IN OUT 1 M 16 2 MODELS HP_OWER 90 IN OUT 1 M ...
Страница 30: ...HP OWER 30 16 3 MODELS HP_OWER 120 150 IN OUT 1 M ...
Страница 31: ...HP_OWER 31 17 WIRING DIAGRAMS 17 1 MODELS HP_OWER 60 90 Temp Sensor Heat Sink ...
Страница 32: ...HP OWER 32 17 2 MODEL HP_OWER 120 Temp Sensor Heat Sink ...
Страница 33: ...HP_OWER 33 17 3 MODEL HP_OWER 150 Temp Sensor Heat Sink CN604 CN607 DC DC1 DC2 DC DC1 DC2 20A 5mH Reactor ...
Страница 35: ......