Solenoid drive
Series MG.., MG..A, MG..A..C (no explosion protection)
Series MG..Xn, MG..A..Xn, MG..A..C..Xn (with - protection
for the intended use in zone 2) in accordance with
2014/34/EU (ATEX 95))
A
B
Solenoid drive Xn- version IP 54 and IP 65**
In accordance with DIN EN 60079-0, as well as the inner
n
C
earth connection, version type “Xn” solenoid actuators
have an additional outer earth connection,
with a conducting connection between them. The outer
earth connection is suitable for connecting a maximum
of two equipotential bonding conductors, each with a
cross- section of up to 6mm².
Minimum cross-sectional area of earthing conductors
Cross-sectional area of the phase
conductor of the installation, S
mm²
Minimum cross-sectional area of
the associated protective
conductor, S mm²
S
≤
16
S
16 < S
≤
35
16
S > 35
0,5 S
Protective conductor connection
The solenoid actuator must always be integrated in the equipo-
tential bonding. A connecting facility is available for this
purpose in the vicinity of the magnetic coil connecting terminal.
NOTICE!
The solenoid drive must additionally be earthed
via the external earthing connection on the
housing.
** encapsulated with cast resin up to the terminal strip
Dimensions
Solenoid
MG...
A
B
ØC
D
E
Weight in kg
IP 54
IP 65
004
100
60
80
-
152
1,6
1,7
005
100
60
80
-
152
1,6
1,7
008
120
73
102
-
163
3,2
3,5
010 (A)
159
88
127
-
176
6,0
7,0
012 (A)
159
97
127
-
176
6,6
7,2
014 (A)
201
120
153
-
189
10,5
11,7
016 (A)
201
134
153
152
189
11,7
12,5
018 (A)
223
152
191
171
208
19,0
22,2
019 (A)
223
152
191
171
208
21,3
24,5
020 (A)
256
182
230
-
227
36,3
40,0