S9500-30XS Hardware Installation Guide | 4
•
Cooling: The S9500-30XS airflow direction is front-to-back. Make sure the equipment on
the same rack have the same airflow direction.
Figure 3.
Figure 4.
Preparation Check List
Task
Check
Date
Power voltage and electric current requirement
DC version
: -36 to -75V DC, 16A maximum x2 or;
AC version:
100 to 240V, 6A maximum x2
Installation spacing requirement
S9500-30XS spacing requires a height of
1RU (1.75”/4.5cm
), a width
of
19”
(48.3cm) in width, and a depth of 18.89 inches (47.9cm)
Thermal requirement
S9500-30XS working temperature is -40 to 65°C (-40°F to 149°F),
airflow direction is front-to-back
Installation tools required
#2 Philips Screwdriver, 6-AWG wire stripper, and crimping tool
Accessories required
PC with terminal emulation software, console cable, 14-AWG wire
with ring terminal for power, 6-AWG wire for grounding