GENERAL

BEFORE  INSTALLING,  CHECK  THE  SENSOR  MODEL  SELECTED  FOR 
COMPATIBILITY  TO  THE  PROCESS  MEDIA  IN  CONTACT  WITH  THE 
SENSOR AND WETTED PARTS.

J6 pressure switches are activated when a bellows or piston sensor responds 
to a pressure change. This response, at a pre-determined set point, actuates 
a single snap-action switch, converting the pressure signal into an electrical 
signal.  Set point may be varied by turning the internal adjustment screw.  (See 
Part II – Adjustments).

PROOF  PRESSURE*  LIMITS  STATED  IN  THE  LITERATURE  AND  ON 
NAMEPLATES MUST NEVER BE EXCEEDED, EVEN BY SURGES IN THE 
SYSTEM.  OCCASIONAL OPERATION OF UNIT UP TO PROOF PRESSURE 

IS ACCEPTABLE (E.G., START-UP, TESTING).  CONTINUOUS OPERATION SHOULD 
NOT EXCEED THE DESIGNATED OVER RANGE PRESSURE**.
*Proof Pressure
The  maximum  pressure  to  which  a  pressure  sensor  may  be  occasionally 
subjected, which causes no permanent damage (e.g., start-up, testing).  The 
unit may require re-gapping.
**Over Range Pressure
The  maximum  pressure  to  which  a  pressure  sensor  may  be  continuously 
subjected without causing damage and maintaining set point repeatability.

THESE PRODUCTS DO NOT HAVE ANY FIELD REPLACEABLE PARTS.

Please refer to product bulletin for product specifications.  UE product bulletins 
may be found at www.ueonline.com

Part I - Installation

Tools Needed 

-Adjustable wrench

- Phillips head screwdriver

MOUNTING

J6 pressure switches may be mounted and operated in any position. They may 

be surface mounted via the two mounting ears on either side of the enclosure, 

or mounted directly to a rigid pipe by using the pressure connection.

ALWAYS  LOCATE  UNITS  WHERE  SHOCK,  VIBRATION  AND 

TEMPERATURE FLUCTUATIONS ARE MINIMAL.  DO NOT MOUNT UNIT 

IN AMBIENT TEMPERATURES EXCEEDING PUBLISHED LIMITS.
UNIT MAY BE MOUNTED IN ANY POSITION PROVIDED THE ELECTRICAL 

CONDUIT  IS  NOT  FACING  UP.    THE  RECOMMENDED  MOUNTING 

POSITION  IS  VERTICAL  (PRESSURE  CONNECTION  FACING  DOWN), 

SPECIFICALLY WHERE HEAVY CONDENSATION IS EXPECTED.

ALWAYS  HOLD  A  WRENCH  ON  THE  PRESSURE  HOUSING 

HEX  WHEN  MOUNTING  UNIT.    DO  NOT  TIGHTEN  BY  TURNING 

ENCLOSURE.  THIS  WILL  DAMAGE  SENSOR  AND  WEAKEN  
SOLDER OR WELDED JOINTS.

On models supplied with an external manual reset button, be sure to leave 
sufficient  finger  space  over  the  reset  button  for  the  operator  to  reset  the 
switch.

WIRING

DISCONNECT  ALL  SUPPLY  CIRCUITS  BEFORE  WIRING  UNIT.  

WIRE  UNITS  ACCORDING  TO  NATIONAL  AND  LOCAL  ELECTRICAL 

CODES.    MAXIMUM  RECOMMENDED  WIRE  SIzE  IS  14  AWG.    THE 

RECOMMENDED TIGHTENING TORqUE FOR FIELD WIRING TERMINALS IS 7 TO 

17 IN-LBS.

ELECTRICAL  RATINGS  STATED  IN  LITERATURE  AND  ON  NAMEPLATE 

SHOULD NEVER BE EXCEEDED.  OVERLOAD ON A SWITCH CAN CAUSE 
FAILURE ON THE FIRST CYCLE.

Remove the four screws retaining the cover and cover gasket. A 1/2” NPT 
conduit connection is provided on the upper left hand side of the enclosure. 
The three switch terminals are clearly labeled common, normally open and 
normally closed.

For optional switches supplied with lead wires, the following color coding 
applies:

Manual Reset (Option 1530)
SPDT

Common

Violet

Normally Open

Blue

Normally Closed

Black

A  threaded  grounding  boss,  tapped  #10-32,  is  provided  in  the  lower  left 
corner  of  the  enclosure.  Keep  the  wires  as  short  as  possible  to  prevent 
interference  with  the  plunger,  or  the  optional  manual  reset  button  or 
adjustable deadband switch wheel.

6 Series

Pressure Switch

Type J6

IM6-08

UNITED ELECTRIC  
CONTROLS

Installation and Maintenance 

Instructions

Please read all instructional literature carefully and thoroughly before starting.  Refer to the final page for the listing of 
Recommended Practices, Liabilities and Warranties.

IM6-08

Содержание 6 Series

Страница 1: ...ERATURES EXCEEDING PUBLISHED LIMITS UNIT MAY BE MOUNTED IN ANY POSITION PROVIDED THE ELECTRICAL CONDUIT IS NOT FACING UP THE RECOMMENDED MOUNTING POSITION IS VERTICAL PRESSURE CONNECTION FACING DOWN SPECIFICALLY WHERE HEAVY CONDENSATION IS EXPECTED Always hold a wrench on the pressure housing hex wheN mounting unit Do not tighten by turning enclosure This will damage sensor and weaken solder or we...

Страница 2: ...tion code 1520 incorporate a snap switch with integral adjust ment wheel Item C in Fig 2 Turning this wheel raises or lowers the pres sure rise set point The fall set point remains constant To use the adjust able deadband switch Determine set point and deadband values For example a rising set point of 20 psi with a deadband value of 6 psi Set the falling set point at desired deadband value determi...

Страница 3: ... models may be found at www ueonline com IM6 08 Dimension A Models Inches mm NPT 126 160 5 06 128 5 1 4 S126B S164B 5 47 138 9 1 2 218 230 4 31 109 5 1 4 258 274 4 75 120 7 1 4 354 364 4 78 121 4 1 4 610 614 5 72 145 3 1 4 680 4 97 126 2 1 4 ...

Страница 4: ...maintenance and periodic testing is necessary for critical ap plications where damage could endanger property or personnel Electrical ratings stated in literature and on nameplate must not be ex ceeded Overload on a switch can cause damage even on the first cycle Wire unit according to local and national electrical codes using wire size recommended in installation sheet Do not mount unit in ambien...

Отзывы: