31
Maintenance
Factory reset
To return access control panel to the factory settings, perform the following steps:
1.
Open enclosure
2.
Disconnect access control panel
3.
Set jumper FACT
4.
Power up
5.
Wait for six beeps, signaling the successful panel reset
6.
Disconnect panel
7.
Remove jumper FACT, close enclosure
Switching to programming mode
To put access control panel in programming mode do the following:
1.
Do not turn off the power.
2.
Open enclosure
3.
Connect cable to the USB and configure the device using the software
"Configurator"
Replacing the device firmware
1.
De-power the panel
2.
Remove the top cover of panel
3.
Connect the notebook with USB cable to the panel
4.
Using special software, do the replacement of panel firmware
5.
After downloading the software to the access control panel WAIT for or 40-
50 seconds. (If readers are connected wait for 6 short beeps)
Attention! Downloading hardware will only be allowed within the first
10 seconds after access control panel launch.
Factory settings
Communicatior
Ethernet mode enabled, DHCP enabled (no device IP set), no ACS server set
Inputs
Z1
– Z8 are disabled
Outputs
Relays 1-4 are disabled
Readers
Wiegand 42bits