25
Combined Loop- RTE and Door Contact
Panel inputs can be configured for simultaneous use of RTE button and Door
Contact on single loop. In this case the loop breaking means breaking of Door
Contact and (short-circuit) shorted - pressing of RTE button.
The example of combined loops connection to Z5 and Z6 terminals is on the Fig. 14.
Fig. 14.
Connecting combined loops
Z5 and Z6 inputs function assigned as follows:
Z5 - Combined door contact and RTE button of access direction A
Z6 - Combined door contact and RTE button of access direction B
Any of 8 inputs can be assigned as a combined for service of door contact and RTE
button
Integration with the fire alarm system
It is necessary to program the input as "Free Pass" for work with fire alarm system.
Connect fire output of the fire control panel to "Free Pass" input. All access points
controlled by the panel will release on "Free Pass" input violation. The Fire output of
fire control panel can be directly connected to this input. When fire alarm is on, loop
of access control panel, designated as "Free pass", is broken. All access points,
supervised by access control panel, are automatically released and the staff can
freely leave the zone of fire (see Figure 15).