Connecting LoopControl
Panel has eight inputs for connecting the loops supervised with end of line resistors.
Each input functionality programmable. Inputs' functions are:
Door Contact
RTE
Door C RTE
Free pass (A, B, A+ B)
Blocking (A, B, A +B)
Sensors monitoring
The following describes how to connect various types of inputs. After factory reset all
loops have no purpose and are not supervised. All loops work both for closing and
opening.
Normal state of the loop - from 1.4 kOm to 3kOm, Line shortage - less than 1.4 kOm,
the broken line - more than 3 kOm.
It is recommended to use supplied resistors.
Request to Exit button (RTE)
RTE is used for exit through single-sided door. In this case, access point opens
when you press and release RTE. Use this input type for remote door opening
button connection also. For example, to open the door manually, by the secretary or
security guard.
The example of normally open contact RTE buttons connection to Z1 and Z2
terminals is on the Fig. 12.
Fig. 12
. Connection of RTE button
Z1 and Z2 inputs function assigned as follows: