PAGE 1 OF 3 

0421 IH-5457

π

  H-5457, H-5795

WALL MOUNT 

EYEWASH STATION

1-800-295-5510

uline.com

INSTALLATION AND MAINTENANCE

INSTALLATION

•  Unit should be assembled in accordance with the 

parts diagram, installed in close proximity to hazard 

and should be in a clearly identified location, free 
of obstructions.

•  Shut-off valve(s) (supplied by others) should be 

installed and located in accordance with the local 
plumbing code.

•  Back flow prevention device(s) (supplied by others) 

should be installed and located in accordance with 
the local plumbing code.

•  Drain location and waste discharge should be 

installed and located in accordance with the local 
plumbing code.

•  Eyewash water flow pattern shall be positioned 

between 33 and 53 inches from the floor and at 
least 6 inches from the wall or nearest obstruction.

•  Unit should be connected with a recommended 

minimum 1/2" IPS line to a tepid, clean water source 
capable of supplying 30-80 PSI flowing pressure 
for a minimum of 15 minutes. If shut-off valves 

are installed inline, provisions should be made to 

prevent unauthorized shut off.

NOTE: Do not use 3/8" nominal flex connector 
as flow may be insufficient.

•  Where freezing conditions exist, unit must be 

protected from freezing.

•  Performance should be verified after installation. 

Check for any leaks while all valves are in the closed 

position. All valves should stay in the open position 
upon activation.

•  With the eyewash valve in the fully opened position 

and using a test gauge, the spray pattern should 

meet required pattern per ANSI Z358.1. Verify that 
the water is tepid, and flow rate is at least 0.4 GPM 
for eyewash and 3.0 GPM for eye/face wash.

MAINTENANCE

•  All units should be tested on a weekly basis to clear 

supply lines and verify proper activation. Units must 
also be inspected annually to verify the continued 
conformance of required performance standards 
stated above.

ANSI / ISEA Z358.1 COMPLIANCE

•  Location:

 Install eye/face wash unit within 10 

seconds (approximately 55 feet) of hazard, on 
the same level as hazard and with unobstructed 
travel path. Where strong acids or caustics are 
being handled, emergency eye/face wash units 
should be located adjacent to the hazard, and an 
appropriate professional should be consulted for 
advice on the proper distance. 

•  Identification:

 Identify eye/face wash location with 

highly visible sign. Area around eye/face wash unit 
shall be well-lit. 

•  Water Temperature:

 Water delivered by eye/face 

wash shall be tepid (60-100°F). 

•  Training: 

Instruct all employees in the location and 

proper use of eye/face wash units.

•  Maintenance/Inspection: 

Activate plumbed eye/

face wash units at least weekly. Inspect all eye/face 

wash units annually for compliance with standard. 