Tyco TYFH-T-1-0700 Скачать руководство пользователя страница 1

Model FH-1

Flexible Hose

Available in Asia and Pacific Territories Only

Page 1 of 8 

JUNE 2021 

TFP725

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

TYCO Model FH-1 Flexible Hose can be 

used in wet sprinkler systems between 

the branchline and sprinkler when 

installed in accordance with NFPA 13, 

13D, and 13R. Flexible Hose provides 

a unique sprinkler drop assembly com-

prised of the following components:

•  Stainless steel flexible hose with 

two slip nuts

•  Branchline inlet nipple
•  Straight sprinkler reducer
•  Reducer bracket, bar fixing clamps, 

and support bar

Using Model FH-1 Flexible Hose saves 

time and cost because the system can 

be installed in false ceilings without 

cutting and threading pipes associ-

ated with installing a drop, arm-over, 

and elbows. Model FH-1 Flexible Hose 

makes it possible to test and charge 

the system with water before installing 

the ceiling grid. After the ceiling grid 

is in position, the Model FH-1 Flexible 

Hose can be reshaped to suit the final 

sprinkler location without draining the 

system.
Model FH-1 Flexible Hose is installed 

quickly without large and expensive 

tools. Ideal applications include offices, 

schools, libraries, hospitals, and shop-

ping complexes.

NOTICE

Model FH-1 Flexible Hose described 

herein must be installed and main-

tained in compliance with this docu-

ment and with the applicable standards 

recognized by the Approval agency, in 

addition to the standards of any other 

authorities having jurisdiction. Failure 

to do so may impair the performance 

of these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Technical 

Data

Approvals

UL Listed (See Table A) 

FM Approved (See Table B)

Nominal Assembly Lengths

700 mm, 1000 mm, 1200 mm, 

1500 mm, 1800 mm

Styles

Braided and Unbraided

Inlet Connection

ISO 7-R 1

Outlet Connections

1/2 in. NPT 
3/4 in. NPT

Maximum Service Pressure

13,8 bar (See Table A) 

12,1 bar (See Table B)

Maximum Ambient Temperature

107°C

Discharge Coefficient

See Tables A and B

Minimum Installation Bend Radius

See Tables A and B

Bending Angles (Flow Direction)

Up to 180 degrees

Materials of Construction

The Flexible Hose is AISI (American 

Iron and Steel Institute) Type 304 Stain-

less Steel. The connection at each end 

of the Flexible Hose utilizes a Slip Nut, 

NBR O-Ring, and Nylon 66 Washer. 

The Inlet Nipple, Sprinkler Reducer, the 

Reducer Bracket, Bar Fixing Clamps, 

and Support Bar are Steel.

Содержание TYFH-T-1-0700

Страница 1: ...position the Model FH 1 Flexible Hose can be reshaped to suit the final sprinkler location without draining the system Model FH 1 Flexible Hose is installed quickly without large and expensive tools I...

Страница 2: ...1000 1 2 80 6 3 102 13 7 TYFH O 1 1200 1200 1 2 80 6 3 102 15 5 TYFH O 1 1500 1500 1 2 80 6 3 102 20 1 TYFH O 1 1800 1800 1 2 80 6 3 102 21 0 Unbraided 13 8 bar 3 4 Inch NPT TYFH O 3 0700 700 3 4 115...

Страница 3: ...or Acoustical Tile and Lay in Panel Ceilings ASTM C636 Standard Practice for Installation of Metal Ceiling Suspen sion Systems for Acoustical Tile and Lay in Panels Model FH 1 Hose connections have be...

Страница 4: ...ADED SLIP NUT HOSE THREADED SLIP NUT CEILING GRID T BAR DROP IN CEILING PANEL SUPPORT BAR SYSTEM BRANCHLINE INLET NIPPLE BRANCHLINE FITTING NOT INCLUDED BAR FIXING CLAMP WITH HEX SCREWS ISO 7 R 1 PIPE...

Страница 5: ...d to avoid mismatched threads REDUCER BRACKET REDUCER BRACKET CEILING GRID T BAR DROP IN CEILING PANEL CEILING GRID T BAR DROP IN CEILING PANEL SUPPORT BAR SUPPORT BAR 95 mm BAR FIXING CLAMP 58 mm BAR...

Страница 6: ...e Hose into a curve s that locates Sprinkler Reducer in area where the sprinkler will be located Do not twist hose and ensure that bend arc is large and smooth Adhere to minimum bend radius in accorda...

Страница 7: ...2 1 bar pressure specify assembly length specify 1 2 in NPT or 3 4 in NPT con nection and P N specify per Table A or B REPLACEMENT PARTS Inlet Nipple Specify Inlet Nipple for Model FH 1 Flexible Hose...

Страница 8: ...NTERNATIONAL BUILDING CODE and IBC are registered trademarks of the International Code Council 1400 Pennbrook Parkway Lansdale PA 19446 Telephone 1 215 362 0700 2021 Johnson Controls All rights reserv...