Document No: LT0499
RDU Mk2 Installation & Programming Manual
Programming Part 2
Issue 1.02
8 April 2015
Page 7-3
7.2
CONFIGURING ZONES
7.2.1
ZONE CONFIGURATION OPTIONS
The following options can be programmed individually for each zone or zone range, or
globally for all zones. The global options apply to all zones 1 to 528 that don't appear
explicitly in the zone/ zone range list. The default settings are shown in Table 6.5.1.
1. MapFF
If enabled (set to ‘Y’), the zone will be entered into the FF alarm list when an alarm
occurs on the zone.
2. AlmSndr
If enabled, the alarm buzzer will be activated for a new alarm on the zone. The global
option "zone alarm buzzer" must also be enabled. Refer section 6.4.4.12.
3. MultiAlm
If enabled, multiple entries in the alarm list will be created for the specified zone, one for
each point that goes into alarm. The FIP must also be configured to send the point
alarm information, i.e., in F4000/MX4428 “Create multiple causes” must be enabled and
an appropriate text name should be assigned to each point.
4. AckTx
This parameter selects whether the RDU can send an ACK command to the FIP for the
specified zones. If enabled, then when an alarm is locally acknowledged by pressing the
ACK key, if there are no other unacknowledged alarms for that zone, a zone ACK
command will be sent to the FIP. This may result in alarm entries in the alarms list of
other panels becoming acknowledged, for that zone. If there are other locally
unacknowledged alarms for the zone, then they must all be acknowledged first before a
zone ACK command is sent to the FIP.
5. AckRX
“Acknowledge receive”. This option selects whether an acknowledgment received from
the FIP for the zone should be applied to an alarm for the zone in the local alarm list. If
AckRx is disabled, then an alarm for the zone must be acknowledged locally.
6. LocAck
“Local Acknowledge”. This option selects whether an alarm for the specified zone can
be acknowledged locally. If LocAck is disabled, then the AckRX option should be
enabled otherwise the alarm can never be acknowledged.
7. ResetFF
If disabled, a reset command cannot be applied to the zone at the RDU. If enabled, a
reset command can be initiated for the zone locally, and sent to the FIP. For a reset
command in the FF alarm list, if there are other alarms in the alarm list for the same
zone, then the alarm being reset is removed from the alarm list, but no reset command is
sent to the FIP. If there are no other alarms in the list for the zone, then a reset
command is sent to the FIP for the zone.
8. IsoFF
If enabled, an isolate command can be initiated for the zone locally, and sent to the FIP.
For an isolate command in the FF alarm list, an isolate command is sent to the FIP only
if there are no other unacknowledged alarms in the alarm list at the RDU for the same
zone. All alarms for the zone must be acknowledged before the zone can be isolated.
Содержание RDU Mk2
Страница 58: ...RDU Mk2 Installation Programming Manual Document No LT0499 Programming Part 1 Page 6 4 8 April 2015 Issue 1 02...
Страница 59: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 1 Issue 1 02 8 April 2015 Page 6 5...
Страница 61: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 1 Issue 1 02 8 April 2015 Page 6 7...
Страница 105: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 2 Issue 1 02 8 April 2015 Page 7 9...