RDU Mk2 Installation & Programming Manual
Document No: LT0499
Programming Part 1
Page 6-22
8 April 2015
Issue 1.02
Option 1
Brigade Test is decribed in Section 6.4.4.5.
Option 2
All zones isolated is described in Section 6.4.4.6.
Option 3
Printer Setup is described in Section 6.4.4.7.
Option 4
Common LEDs is described in Section 6.4.4.8.
Pressing right arrow again shows:
1:Daylight saving start 2:Daylight saving end 3:Mains/battery <>
Options 1 and 2
Daylight Start and End are described in Section 6.4.4.9.
Option 3
Mains/Battery is described in Section 6.4.4.10.
Pressing right arrow again shows:
1:Keys enable 2:Buzzer options 3:New Zealand options
Option 1
Keys enable is described in Section 6.4.4.11.
Option 2
Buzzer options is described in Section 6.4.4.12.
Option 3
New Zealand Mode options are described in Section 6.4.4.13.
6.4.4.1
FF Options
From the "global data" menu, option 1:FF options produces the following six "pages" of
menus.
FF Pg 1 1:FF alarm source 2:FF Auto ack
FF Pg 2 1:FF type 2:Global commands
FF Pg 3 1:Show FIP zone names in FF 2:FF display cause by default
FF Pg 4 1:New cause new alarm 2:Multiple cause updates
FF Pg 5 1:Switch to newest alarm 2:Show zone number on FF display
FF Pg 6 1:Show isol alarms in FF 2:Show point text in FF for zone
1. FF alarm source
This can be set to one of three values 1:LCD messages 2:LED messages 3:Both LCD
& LED messages. This option is normally set to "LCD messages". For connection to a
FIP which doesn't send LCD messages, this option can be set to "LED messages".
There are two types of messages that can be sent on the RZDU bus by a fire panel -
"LED messages" and "LCD messages". LED messages contain zone status (alarm,
fault, isolate) for up to 528 zones. LCD messages contain "new FF alarm" information
and are sent by the FIP when a zone goes into alarm. LCD messages contain zone text
and point text associated with the zone/point that caused the alarm. If "LCD messages"
are enabled as an FF alarm source, then when an LCD FF alarm message is received
from the FIP, an entry is added to the FF alarm list. If "LED messages" are enabled as
an FF alarm source, then when the zone status in an LED message received from the
FIP indicates a new alarm on a zone, an entry is added to the FF alarm list for the zone.
For an FF alarm generated from an "LED message", the zone text shown is taken from
the zone names programmed in the RDU.
2. FF Auto Ack
If enabled, alarms entered into the local FF alarm list are acknowledged automatically.
3. FF type
This parameter selects either type 2 or type 3 FF operation. AS4428.1 requires type 3
FF operation. Type 2 operation might be used with legacy AS1603.4 systems.
Содержание RDU Mk2
Страница 58: ...RDU Mk2 Installation Programming Manual Document No LT0499 Programming Part 1 Page 6 4 8 April 2015 Issue 1 02...
Страница 59: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 1 Issue 1 02 8 April 2015 Page 6 5...
Страница 61: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 1 Issue 1 02 8 April 2015 Page 6 7...
Страница 105: ...Document No LT0499 RDU Mk2 Installation Programming Manual Programming Part 2 Issue 1 02 8 April 2015 Page 7 9...