General
Description

The Series TY300-FRB, 5.6 K-factor
Sprinklers described in this data sheet
are quick responding, decorative 3 mm
glass bulb type spray sprinklers. Their
maximum rated service  pressure  of
300 psi (20,7 bar) makes them an ex-
cellent choice for systems that other-
wise would require the use of a pres-
sure control valve to reduce the static
pressure to 165 psi (11,4 bar), when
conventional 175 psi (12,1 bar) maxi-
mum rated pressure sprinklers are util-
ized. One of the most common uses for
the TY300-FRB Sprinklers is in fire
protection systems for high rise build-
ings.

The recessed version of  the Series
TY300-FRB Sprinklers are intended
for use in areas with a finished mount-
ing surface (i.e., ceiling or wall, as ap-
plicable). They use either a two-piece
Style 10 Recessed Escutcheon with
1/2 inch (12,7 mm) of recessed adjust-
ment or up to 3/4 inch (19,1 mm) of
total adjustment from the flush pen-
dent/sidewall position, or a two-piece
Style 20 Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent/sidewall position. The adjustment
provided by the Recessed Escutcheon
reduces the accuracy to which the
fixed pipe to the sprinklers must be cut.

Corrosion resistant  coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.

WARNINGS

The Series TY300-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-

ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction.

Failure to do so may

impair the performance of these de-
vices.

The owner is responsible for maintain-
ing their fire protection system and de-
vices in  proper operating  condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.

Model/Sprinkler
Identification
Numbers

TY3105 -

Upright 5.6K, 1/2"NPT

TY3205 -

Pendent 5.6K, 1/2"NPT

TY3305 -

HSW

5.6K, 1/2"NPT

TY3307 -

EC HSW 5.6K, 1/2"NPT

D

uP

on

t

R

eg

is

tere

d

T

rad

ema

rk

Series TY300-FRB — 5.6 K-factor
High Pressure Sprinklers, 300 psi (20,7 bar)
Quick Response, Standard & Extended Coverage

Page 1 of 8

TFP642

JULY, 2004

Technical Services:

Tel: (800) 381-9312 / Fax: (800) 791-5500

IMPORTANT

Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.

OBSOLETE

Содержание TY300-FRB

Страница 1: ...e testing is not representative of all possible cor rosive atmospheres Consequently it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corro sive environment The effects of ambi ent temperature concentration of chemicals and gas chemical velocity should be considered as a minimum along with the corrosive nature of the chemical to which ...

Страница 2: ...w rate criteria Only the Style 10 or 20 Recessed Es cutcheon as applicable is to be used for recessed installations Installation The Series TY300 FRB Sprinklers must be installed in accordance with the following instructions NOTES Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb With the sprinkler held horizontally a small air bubble should b...

Страница 3: ... to the pipe threads hand tighten the sprinkler into the sprinkler fitting Step 3 Tighten the sprinkler into the sprinkler fitting using only the W Type 6 Sprinkler Wrench Ref Figure 10 With reference to Figure 2 or 3 the W Type 6 Sprinkler Wrench is to be applied to the wrench flats The Series TY300 FRB Recessed Horizontal and EC Horizontal Side wall Sprinklers must be installed in accordance wit...

Страница 4: ...essed Escutcheon Installed with Style 20 1 2 NPT 1 2 Total Adjustment Recessed Escutcheon Frame and deflector only Listings and approvals apply to color Special Order TABLE A LABORATORY LISTINGS AND APPROVALS K 5 6 1 2 NPT PENDENT TY3205 and UPRIGHT TY3105 135 F 57 C Orange 155 F 68 C Red 175 F 79 C Yellow 200 F 93 C Green 286 F 141 C Blue 1 2 5 RECESSED HSW TY3305 Figure 6 135 F 57 C Orange 155 F...

Страница 5: ... 1 4 6 4 mm 3 4 19 1 mm 3 2 mm 1 8 5 8 1 4 FACE OF FITTING SPRINKLER 15 9 6 4 mm 2 7 8 DIA SERIES TY FRB FIGURE 5 SERIES TY300 FRB RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO PIECE 1 2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 5 6 K FACTOR 1 2 INCH NPT FIGURE 7 SERIES TY300 FRB RECESSED HORIZONTAL SIDEWALL SPRINKLER WITH TWO PIECE 1 2 INCH TOTAL ADJUSTMENT STYLE 20 RECESSED ESCUTCHEON 5 ...

Страница 6: ... re placed Also replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb Ref Installation Section Frequent visual inspections are rec ommended to be initially performed for corrosion resistant coated sprinklers after the installation has been com pleted to verify the integrity of the cor rosion resistant coating Thereafter annual inspections per NFPA 25 should suffice ho...

Страница 7: ...r pendent sprinklers must be located outside of the maximum listed pro tection area of the extended coverage sidewall sprinkler being utilized 5 6 K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER TY3307 Response Coverage Minimum Minimum Deflector Sprinkler Minimum Rating Area 1 Flow 2 Pressure 2 To Ceiling Temperature Spacing 4 Ft x Ft m xm GPM LPM PSI BAR Distance 3 In mm Rating F Ft m Quick 16 ...

Страница 8: ...ES EXPRESS OR IMPLIED INCLUDING WARRANTIES OF MERCHANTABILITY AND FIT NESS FOR A PARTICULAR PUR POSE Ordering Procedure When placing an order indicate the full product name Refer to the Price List for complete listing of Part Numbers Contact your local distributor for avail ability Sprinkler Assemblies with NPT Thread Connections Specify Specify Model SIN 3 mm Bulb Type 5 6 K factor specify tem pe...

Отзывы: