Quick Response
Extended Coverage
Horizontal Sidewall Sprinklers
SuperNova™ S124
K=5.6, 1/2" NPT
GENERAL DESCRIPTION
The Star SuperNova S124, 5.6 K-Factor, QR-EC Horizon-
tal Sidewall Sprinklers are quick response - extended cov-
erage, fusible solder type spray sprinklers designed for
use in hydraulically calculated sprinkler systems in light
hazard, commercial occupancies such as churches, res-
taurant seating areas, hotels, educational facilities, of-
fices, etc. With coverage areas up to 16 feet (4,9 m) wide
by 20 feet (6,1 m) long, they are designed for installation
along a wall or the side of a beam and just beneath a
smooth and level ceiling. Horizontal sidewall sprinklers
are commonly used instead of pendent or upright sprin-
klers because of aesthetics or building construction con-
siderations, where piping across the ceiling is not desir-
able.
WARNINGS
The SuperNova S124 Sprinklers described herein must
be installed and maintained in compliance with this docu-
ment, as well as with the applicable standards of the Na-
tional Fire Protection Association, in addition to the stand-
ards of any other authorities having jurisdiction. Failure to
do so may impair the integrity of these devices.
The owner is responsible for maintaining their fire protec-
tion system and devices in proper operating condition.
The installing contractor or sprinkler manufacturer should
be contacted relative to any questions.
OPERATION
The fusible link (heat collector) assembly is comprised of
two link halves which are joined together by a thin layer
of solder. When the rated temperature is reached, the sol-
der melts and the two link halves separate, which then al-
lows the sprinkler to activate and flow water.
TECHNICAL DATA
Approvals
UL and ULC Listed. FM Approved.
NYC Accepted (MEA 188-99-E).
(The approvals apply only to the service conditions indi-
cated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
1/2 inch NPT
Discharge Coefficient
K = 5.6 GPM/psi
1/2
(80,6 LPM/bar
1/2
)
Temperature Rating
165°F/74°C
Finish
Sprinkler: Natural Brass or Chrome Plated
Physical Characteristics (Ref. Figure 1)
The SuperNova S124 utilizes a bronze frame. The strut
and hook are bronze; the button and deflector are brass;
the orifice seal is Teflon
; and, the two halves of the fus-
ible link assembly are nickel.
DESIGN CRITERIA
The 5.6 K-Factor, SuperNova S124 (SIN S1888) QR-EC
Horizontal Sidewall Sprinklers must only be installed and
utilized for the protection of Light Hazard Occupancies un-
der smooth and level ceilings, as well as in accordance
with the criteria given in Table A or B, as applicable. Instal-
lation of SuperNova S124 Sprinklers in recessed escutch-
eons will void all sprinkler warranties, as well as possibly
void the sprinkler’s Approvals and/or Listings.
SIN S1888