STAR SPRINKLER INC.
Page 6
2-7.1.10
7071 S. 13th Street • Suite 103
Oak Creek, WI 53154
414-570-5000 • 800-558-5236
PRINTED IN U.S.A. 6-99
OBSOLETE
Страница 1: ...icable standards of the National Fire Protection Association in addition to the standards of any other authorities having jurisdiction Failure to do so may impair the integrity of this device The owne...
Страница 2: ...ts minimum ex pected value Actual sprinkler demand for the most hy draulically remote fire sprinkler should be in accordance with the manufacturer s minimum acceptable flow and pressure but the minimu...
Страница 3: ...the domestic system The inlet to the Domestic Control Valve is to be located within 12 inches 300 mm of the Domestic Port of the S370 Valve 5 The Drain and Flow Test Connection Ref Figure A must be m...
Страница 4: ...verifying that at least three water outlets in the do mestic system can flow full at the same time If the water outlets flow full the S370 Valve is set and ready for service and the water outlets on...
Страница 5: ...hat there is no flow from the fire sprinkler system piping such as at the Inspector s Test Connection Wait a minimum of ten seconds Re open the Domestic Control Valve and then recheck that the domesti...
Страница 6: ...STAR SPRINKLER INC Page 6 2 7 1 10 7071 S 13th Street Suite 103 Oak Creek WI 53154 414 570 5000 800 558 5236 PRINTED IN U S A 6 99 O B S O L E T E...