any water flow to the Domestic Flow Port is diverted to
the Fire Sprinkler Flow Port.

The contours of the Piston have been specifically config-
ured to minimize its upward movement except under the
level of sustained fire sprinkler system flow resulting from
operation of one or more fire sprinklers. However, be-
cause most fire sprinkler systems contain air pockets, the
Piston will tend to move momentarily upward if there is a
surge in supply pressure. The momentary opening and re-
closing of the Piston at the Fire Sprinkler Line Seals will
trap a portion of the pressure increase within the fire
sprinkler system. The trapping of pressure increases
within the fire sprinkler system will help to reduce the pos-
sibility of a subsequent surge in the supply pressure from
causing the waterflow detector to signal a false alarm.

As indicated above, domestic system usage may reduce
the pressure available to the fire sprinkler system. How-
ever, when utilizing the S370 Valve, it is not necessary to
take into account the complex hydraulic modeling of the
domestic system that would otherwise be required to de-
termine the minimum possible residual (flowing) pressure
that would be available to the fire sprinkler system.

For operation of the S370 Valve, it is only necessary to de-
sign the fire sprinkler system, from the water supply main
to the most hydraulically remote sprinkler, to provide a
minimum single sprinkler flow of 5 GPM (19 LPM), when
the supply pressure at the main is at its minimum ex-
pected value. Actual sprinkler demand for the most hy-
draulically remote fire sprinkler should be in accordance
with the manufacturer’s minimum acceptable flow and
pressure, but the minimum flow must be at least 5 GPM
(19 LPM).

DESIGN CRITERIA

In order for the S370 Valve to automatically operate once
a fire sprinkler operates, the fire sprinkler system from
the water supply main to the most hydraulically remote
sprinkler must be designed to provide a minimum single
sprinkler flow of 5 GPM (19 LPM), when the water supply
pressure at the water supply main is at its minimum ex-
pected value.

NOTES

The minimum single sprinkler flow rate of 5 GPM (19
LPM), required for use with the S370 Valve, does not
take precedence over any more hydraulically demanding
single or multiple sprinkler flow rates specified for the resi-
dential sprinklers being utilized.

INSTALLATION

The Model S370 Automatic Residential Domestic Shut-
Off Valve must be installed in accordance with the follow-
ing instructions:

NOTE

A fire sprinkler water supply connection to a public water
supply is usually subject to local regulations concerning
metering and backflow prevention requirements. Consult
with the local water authorities concerning local require-

STAR SPRINKLER INC.

Page 2

2-7.1.10

FIGURE 1

MODEL S370 AUTOMATIC RESIDENTIAL

DOMESTIC SHUT-OFF VALVE

4-5/8"

(117.5 mm)

4-9/16"

(115.9 mm)

5-3/8" DIA.

(136.5 mm)

3-3/4"

(95.3 mm)

9-3/16"

(233.4 mm)

5

2

3

7

4

1

FIRE

PORT,

2" NPT

SUPPLY

PORT,

2" NPT

DOMESTIC

6

PORT,

2" NPT

SPRINKLER

WATER

NO. DESCRIPTION . . . . . QTY.

1

Body . . . . . . . . . . . 1

2

Cover . . . . . . . . . . 1

3

Piston . . . . . . . . . . 1

4

Spring . . . . . . . . . . 1

5

Fire Sprinkler Line Seal . 2

6

Domestic Line Seal . . . 1

7

Cover O-Ring . . . . . . 1

FIGURE 2

TYPICAL INSTALLATION