RAPID RESPONSE Model RSV-1 Residential
Shut-Off Valve, Dual-Purpose Water Supply,
Domestic and Fire Sprinkler System

Page 1 of 6 

JULY 2016 

TFP980

Worldwide

Contacts

www.tyco-fi re.com

General
Description

The TYCO RAPID RESPONSE Model 
RSV-1 Residential Shut-Off Valves are 
intended for use in dual-purpose resi-
dential water supply piping that serves 
both domestic and residential fi re pro-
tection sprinkler system needs. The 1 
Inch (DN25) Valve is intended for NFPA 
13D system needs, whereas the 2 Inch 
(DN50) Valve is intended for systems 
designed  in  accordance  with  either 
NFPA 13, 13D, or 13R.

When a fi re sprinkler operates, the 
Model RSV-1 Residential Shut-Off 
Valve automatically diverts the avail-
able water supply to the fi re sprin-
kler system. Consequently, when the 
Model RSV-1 Valve is utilized, the 
system designer does not need to 
add the domestic fl ow demand to the 
fi re sprinkler system fl ow demand, as 
would otherwise be required by NFPA 
13D or 13R.

Consider use of the Model RSV-1 Res-
idential Shut-Off Valve when either 
the water supply cannot adequately 
provide for both the domestic design 
demand and the fire sprinkler flow 
demand, or it is necessary to increase 
the effectiveness of the fi re sprinkler 
system by automatically diverting the 
domestic fl ow.

The Model RSV-1 Residential Shut-
Off Valve maximizes the effective use 
of an existing water supply. There-
fore, in areas with limited water sup-
plies, it may eliminate the need to add 
costly pumps, pressurized reservoirs, 
or electrically operated domestic shut-
off valves. The Model RSV-1 Valve has 
a built-in check valve in the fi re sprin-
kler  system  outlet  that  eliminates  the 
need for a separate check valve. Also, 
the Model RSV-1 Valve automatically 
resets, thereby eliminating the need for 
valve disassembly after a fi re sprinkler 
system test or operation.

NOTICE

The Model RSV-1 Residential Shut-
Off Valves described herein must be 
installed and maintained in compliance 
with this document, as well as with the 
applicable standards of the National 
Fire Protection Association, in addi-
tion to the standards of any authorities 
having jurisdiction. Failure to do so may 
impair the integrity of this device.

The owner is responsible for main-
taining their fire protection system 
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any 
questions.

Technical 
Data

Approvals

UL and C-UL Listed
Certifi ed to all requirements of
NSF/ANSI 61, Annex G and NSF/ANSI 372

Notes:

The 1 Inch (DN25) Model RSV-1 Resi-
dential Shut-Off Valve is suitable for use 
in water supply arrangements for resi-
dential fi re sprinkler systems designed 
per NFPA 13D.

The 2 Inch (DN50) Model RSV-1 Resi-
dential Shut-Off Valve is suitable for use 
in water supply arrangements for resi-
dential fi re sprinkler systems designed 
per NFPA 13, 13D, or 13R.

Maximum Pressure

175 psi (12,1 bar)

Weight

1 Inch (DN25): 11 lbs. (5 kg) 
2 Inch (DN50): 29 lbs. (11 kg)

Pressure Loss

Refer to Graphs A and B

Patents

2 Inch (DN50) Model RSV-1 Valve 
Patent Pending

Physical Characteristics

1 Inch (DN25) Valve

Body  . . . . . . . . . . . . . . . . . . . . . . . . Copper Alloy
Top and Bottom Cover . . . . . . . . . . Copper Alloy
Upper Cap . . . . . . . . . . . . . . . . . . . . . . . . . . Brass
Bottom Seal  . . . . . . . . . . . . . . . . . . . . . . . . Brass
Piston  . . . . . . . . . . . . . . . . . . . . . . . . . . .  Plastic

*

Differential Ring  . . . . . . . . . . . . . . . . . . .  Plastic

*

Sleeve . . . . . . . . . . . . . . . . . . . . . . . . . . .  Plastic

*

Upper and Lower Seals  . . . . . . . . . . . . . .  EPDM
O-Rings . . . . . . . . . . . . . . . . . . . . . . . . . . Buna-N
Piston Spring  . . . . . . . . . . . . . . .  Stainless Steel
Piston Screws . . . . . . . . . . . . . . .  Stainless Steel
Cap Screw . . . . . . . . . . . . . . . . . .  Stainless Steel

2 Inch (DN50) Valve

Body and Cover  . . . . . . . . . . . . . . . Copper Alloy
Piston Insert  . . . . . . . . . . . . . . . . . . Copper Alloy
Bottom Seal  . . . . . . . . . . . . . . . . . . Copper Alloy
Piston Cover . . . . . . . . . . . . . . . . . . . . . .  Plastic

*

Insert Sleeve . . . . . . . . . . . . . . . . . . . . . .  Plastic

*

Piston Seal  . . . . . . . . . . . . . . . . . . . . . . . .  EPDM
O-Rings . . . . . . . . . . . . . . . . . . . . . . . . . . .  EPDM
Piston Spring  . . . . . . . . . . . . . . .  Stainless Steel
Piston Nut . . . . . . . . . . . . . . . . . .  Stainless Steel
Retainer Ring  . . . . . . . . . . . . . . .  Stainless Steel

*Glass Reinforced Polyphenylene Oxide

Содержание RAPID RESPONSE RSV-1

Страница 1: ...ally resets thereby eliminating the need for valve disassembly after a fire sprinkler system test or operation NOTICE The Model RSV 1 Residential Shut Off Valves described herein must be installed and maintained in compliance with this document as well as with the applicable standards of the National Fire Protection Association in addi tion to the standards of any authorities having jurisdiction F...

Страница 2: ...ossible resid Design Criteria The TYCO RAPID RESPONSE Model RSV 1 Residential Shut Off Valve must be installed vertically with the Water Supply Port at the bottom the Fire Sprinkler Port at the top and the Domestic Port at the side Ref Figures 4 and 5 Figure 1 shows the typical installation arrangement Refer to the Installation section for additional design considerations Water Supply Requirements...

Страница 3: ...ly when performing hydraulic design calculations for the fire sprinkler system you do not need to consider trickle flow through the Model RSV 1 Valve Internal By Pass Restriction into the domestic system When using the 2 inch RSV 1 the maximum flow rate through the Internal By Pass Restriction when the Model RSV 1 Valve is in the operated position is no greater than 1 5 GPM 5 7 LPM for a typical r...

Страница 4: ... to or less than the smallest K factor sprinkler in the system downstream of the Water flow Detector Step 6 Apply pipe thread sealant spar ingly only to the male pipe threads that are to be assembled to the three ports of the Model RSV 1 Valve The use of a non hardening pipe thread sealant such as TEFLON is recommended Valve Setting Procedure Perform steps 1 through 9 when initially filling the fi...

Страница 5: ...E DOMESTIC SEAT OPERATED STANDBY SUPPLY SUPPLY TO FIRE SPRINKLERS TO DOMESTIC FIRE SPRINKLER FLOW PASSAGE SUPPLY PORT FIRE SPRINKLER PORT DOMESTIC PORT FIRE SPRINKLER SEAT SUPPLY PORT FIRE SPRINKLER SEAT DOMESTIC PORT FIRE SPRINKLER PORT PISTON ASSEMBLY DOMESTIC SEAT INTERNAL BY PASS RESTRICTION PISTON ASSEMBLY DOMESTIC FLOW PASSAGE DOMESTIC SEAT FIGURE 4 1 INCH DN25 MODEL RSV 1 RESIDENTIAL SHUT O...

Страница 6: ... for the inspection testing and maintenance of their fire protection system and devices in compliance with this document as well as with the applicable standards of the National Fire Protection Associa tion e g NFPA 25 in addition to the standards of any authority having juris diction Contact the installing contrac tor or product manufacturer regarding any questions Automatic sprinkler systems sho...